14 | Mounting

Specifications
Maximum output per connection
• PC0, PC1
• A0, IA1
Capturing range for the flow and
return temperature sensor
• Lower fault limit
• Display range
• Upper fault limit
Capturing range, outside
temperature sensor
• Lower fault limit
• Display range
• Upper fault limit
Permitted ambient temp.
IP rating
Protection class
ID no.
Table 3
2.6

Additional accessories

For detailed information about suitable accessories, please refer to the
catalogue.
• User interface: weather-compensated controller with outside
temperature sensor or room temperature-dependent controller;
connect to BUS (do not connect to BUS1, BUS2, BUS3 or BUS4);
connect outside temperature sensor to T1
• Flow temperature sensor; connect to T0
• Outside temperature sensor; connect to T1
• Return temperature sensor; connect to T2
• Cascade pump; connect to PC0
• Heating pump; connect to PC1
• Switch for max. output; connect to I2
• Stop switch; connect to I3
• IGM for heat source without EMS, EMS 2 or EMS plus; connect in
accordance with the technical documentation for the IGM (the
MC400 cascade module replaces the ICM)
Installation of additional accessories
▶ Install the additional accessories in accordance with legal
requirements and the instructions supplied.
2.7

Cleaning

▶ If required, wipe the enclosure with a damp cloth. Never use
aggressive or acidic cleaning agents for this.
6 720 816 739 (2015/05)
• 400 W (high-efficiency pumps
permitted; max. 40 A/s)
• 10 W
• < – 10 °C
• 0 ... 100 °C
• > 125 °C
• < – 35 °C
– 30 ... 50 °C
• > 125 °C
0 ... 60 °C
IP44
I
Data plate ( Fig. 22, page 85)
3
Mounting
DANGER: Risk of electric shock!
▶ Before installing this product: completely disconnect
heat appliances and all other BUS nodes from the mains
voltage.
▶ Before commissioning: fit the cover ( Fig. 21,
page 85).
3.1

Installation

▶ Install the module on a wall, ( Fig. 6 to Fig. 8, starting at page 82),
on a mounting rail ( Fig. 9, page 82) or in an assembly.
▶ When removing the module from the mounting rail, refer to Fig. 10 on
page 83.
3.2

Electrical connection

▶ Observe current regulations applicable to power connections, and
use at least cable type H05 VV-...
3.2.1
Connecting the BUS connection and temperature sensor
(extra-low voltage side)
General BUS connection
If the maximum cable length of the BUS connection between
all BUS nodes is exceeded, or if the BUS system is realised
as a ring structure, the system cannot be commissioned.
Maximum total length of BUS connections:
2
• 100 m at 0.50 mm
conductor cross-section
2
• 300 m at 1.50 mm
conductor cross-section
BUS connection between the heat source – and cascade module
▶ Connect the heat sources and lower-level cascade modules directly to
terminals BUS1 ...BUS4 ( overview of the terminal assignment).
BUS connection between the cascade module – user interface –
other modules
▶ If the conductor cross-sections are different, use the junction box to
connect the BUS nodes.
▶ BUS user [B] via junction box [A] in a star ( Fig. 19, page 84, note
the instructions for the user interface and other modules).
Temperature sensor
When sensor leads are extended, apply the following lead cross-sections:
2
• up to 20 m with 0.75 mm
to 1.50 mm
• 20 m up to 100 m with 1.50 mm
2
conductor cross-section
2
conductor cross-section
MC 400