Control And Safety Devices; Electronic Control And Display Module - CIAT DYNACIAT power LG Manuel D'instructions

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

General fault alarm:
Connector
1
2
J3
J3 (CPU)
(CPU)
Remote control: Connect the unit's general fault reporting or
alarm to the terminals on the unit's terminal strip (see wiring
diagram).
• Output specification: 2 A under 250 V.
Automatic operation control:
Connector
1
2
3
J6
J6 (CPU)
(CPU)
CA
Remove shunt "CA" from between the terminals on the unit
terminal strip (see wiring diagram) and connect a "C1" contact
to these terminals (high-quality polarity-free contact).
• Contact open → unit off
• Contact closed → unit authorised to run
• Input specification: 24 V - 15 mA.
Display of the operating state of pump No. 1
Connector
1
2
3
4
J5 (CPU)
• Contact open → Pump off
• Contact closed → Pump in operation
• Input specification: 24 V - 15 mA.
Other connections can be made to the CPU CONNECT2 board
Water pump control
Connector
1
2
14 15 16
J3 (CPU)
Connect the supply to the pump relays between the terminals
of the connector on the main board.
• Output specification: 2 A under 250 V
Setpoint 1/setpoint 2 selector control
Connector
1
2
3
J6 (CPU)
Connect a "C2" contact to the terminals of the connector of the
CPU board (high-quality polarity-free contact)
• Contact open → setpoint 1
• Contact closed → setpoint 2
• Input specification: 24 V - 15 mA

16 CONTROL AND SAFETY DEVICES

16.1 Electronic control and display module

All units in the DYNACIAT
power
fitted with a CONNECT2 microprocessor-controlled electronic
control and display module.
11 12 13 14 15 16
230 V
230 V
Alarm
4
5
6
10
11
C1
5
6
10
11
K
Pump relay No. 2
230 V - 8 A
Pump relay No. 1
230 V - 8 A
Common
4
5
6
10
11
C2
range and its derivatives are
Display for operation at full power (if P111 = max P)
Connector
1
2
J3 (CPU)
Connect the signalling of the unit operating at max.
output to terminals 1 and 2 of the connector on the
CPU board.
• Output specification: 2 A under 250 V.
"Load shedding" function control
Connector
J6
J6 (CPU)
(CPU)
Connector J2
J2
(Circuit board 2) ADD 2
(Carte circuit 2) ADD 2
Connect 1 to 4 contacts to the terminals of the connector of the
CPU board according to the number of the compressors to be
shed. 1 contact per compressor (contact free of any polarity
and of good quality).
• Contact open → normal operation,
• Contact closed → compressor load shedding.
• Input specification: 24 V - 15 mA.
NOTE:
• Connection to be made on site by the customer,
• Precautions for connection. See manual for the regulator
and the electrical diagram of the unit.
Communication
• In the room, a control and display console is used to
run an instant check on the unit; it enables the user to
communicate with the microprocessor, to configure the unit
and to adjust the setpoints.
• Electronic remote control (option):
Installed in the machine room, this will be connected to
the unit by a pair of telephone-type wires (max. distance
1000 m). Description of functions and connection: see
CONNECT2 manual.
• Relay board(s) (option):
This board is installed in a cabinet in the machine room and
can remotely report on all the unit's operating states and
faults by providing contacts which are potential-free when
closed. The board will be connected to the unit by a pair of
telephone-type wires (max. distance 1000 m).
Description
of
functions
CONNECT2 manual.
• Communication with centralised management system
(option).
• See possibility in CONNECT2 manual.
The electronic module controls the operation of the
compressors. Thus, depending on the difference between the
cold water (or hot water) return temperature and the setpoint
temperature
EN - 11
9 10 11
15 16
230 V
1
7
8
9
10
11
stage
N° 1 N° 2
1
7
8
9
stage
N° 3 N° 4
and
connection:
EN
see