Electrical installation
Wiring
Terminal assignment
Motor
Terminal X105
(right part)
Terminal data
Device sizes 1 + 2:
flexible
with wire end ferrule
Device size 3:
flexible
with/without wire end ferrule
52
Labelling
Description
U
Connection of the motor phases
V
W
"
Functional earth
Connect the shields of the motor phases and of the
optional motor brake control separately and with a
surface as large as possible to the shield sheet. Use
EMC wire clamp or EMC shield clamp for fixing.
+
Connection for the PE conductor on the motor side
with M5 ring cable lug
SSP940X105
Max. conductor
cross−section
2
[mm
]
2.5
10/16
l
Tightening torque
[AWG]
[Nm]
12
0.5 ... 0.6
4.5 ... 5.3
6
1.2 ... 1.5
10.6 ... 13.3
EDK94ZPS113 DE/EN/FR/ES/IT 6.0
!
[lb−in]
PZ0