Installation; Extraction Arm - PLYMOVENT DUALGO Manuel D'installation Et D'utilisation

Epurateur fixe des fumées de soudure avec deux bras flexibles
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 28
ATTENTiON
Service, maintenance and repairs must be
performed in accordance with directive TRGS 560
and TRGS 528 by authorised, qualified and trained
persons (skilled) using appropriate work practices.
ATTENTiON
Before you carry out service, maintenance and/or
repair jobs:
- fully disconnect the unit from the mains
Personal protective equipment (PPE)
Wear respiratory protection and protective
gloves during service, maintenance and
repairs.
WARNiNG
The industrial vacuum cleaner that you use during
service and maintenance must meet dust class H
according to EN 60335-2-69 or HEPA class
(efficiency ≥99.97% at 0.3 µm).
4

iNSTALLATiON

4.1
Tools and requirements
You need the following tools and requirements to install the
unit:
- basic tools
- fork-lift truck
4.1.1
To be sourced locally
- wall mounting hardware
- mains cord 4G1.5 (4x1,5 mm²)
- cable gland M20
- option: plug
4
4.2
Unpacking
Make sure that the product is complete. The package contains:
Filter unit
- stationary filter unit, incl. wall bracket
- bolt M10x30 (2) + locknut M10 (2) + washer (4)
- washer M6 (16)
- bolt M6x25 (16)

Extraction arm (2)

In case of DualGo: hose tube arm (2)
- extraction arm (pre-assembled; excl. hose tube)
- hose tube
- hose clamp (2)
- rotating flange
- arm swivel ring, incl. rubber collar
- extraction hood
- hood collar with safety mesh
- washer M20
- hexagon bolt M6x25 (4)
In case of DualGo
: metal tube arm (2)
plus
- extraction arm (pre-assembled)
- rotating flange
- arm swivel ring, incl. rubber collar
- extraction hood
- hood collar with safety mesh
- washer M20
- hexagon bolt M6x25 (4)
Control equipment
- switch box
3. The type of hardware depends on the wall type
4. Alternative: direct connection to the mains + additional main switch
0000111692/150418/A DualGo
3
4.3
Stationary filter unit
ATTENTiON!
Before you install the unit, make sure that the wall
is strong enough. Refer to section 1.4 for the weight
of the unit.
• Refer to Fig. III on page 52 for the recommended
installation height and the hole pattern of the wall bracket.
To install the wall bracket, do the following.
Fig. 4.1
• The wall bracket is temporarily attached to the unit by a
cable tie. Cut the cable tie.
• Install the wall bracket (B) to the wall. Use all 4 mounting
points.
• Lift the unit and insert the hooks (A) in the slots of the wall
bracket.
• Attach the unit to the wall bracket with the bolts, locknuts
and washers (C).
A
B
C
Fig. 4.1 Mounting of the wall bracket
4.4
Arm to stationary unit
To install the extraction arms, do the following.
TiP
Do a balance check of the arm before you fasten the
hoses. Refer to section 6.3.
Fig. 4.2
• Remove the locknut M20 (A) from the hinge rod (E).
• In case of a hose tube arm: put the hose tube over the
internal rods of the arm.
• Move the hose clamp (F) and the arm swivel ring (incl.
rubber collar) (D) over the hinge rod (E).
• Put the washer M20 (C) on the arm swivel ring (D).
• Put the hinge rod (E) in the rotating flange (B).
• Put the hose (G) over the arm swivel ring (D).
• Use the rubber collar to make the connection airtight.
• Attach the hose (G) to the swivel ring (D) with the hose
clamp (F).
• Put the locknut M20 (A) on the hinge rod (E) and tighten it.
• Install the assembly to the filter unit with the 8 bolts
M6x25 + washers M6.
• Do the same procedure for the other extraction arm.
EN - 6

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Dualgoplus

Table des Matières