Technical Data - Parker Hiross StarlettePlus SPS026-ES Manuel D'utilisation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 21
Weight
Model
(Kg)
SPS 026-ES
46
SPS 032-ES
46
SPS 040-ES
47
SPS 052-ES
53
SPS 062-ES
55
SPS 080-ES
100
SPS100-ES
Expansion auto-
Calibration values
matic valve
SPS 026 / 62-ES
2.4 barg (+ 0.1, - 0)
SPS 080 / 100-ES

8.3 TECHNICAL DATA

Ambient Temperature
Refrigerant
R513a
During
transport
and stockage
(Kg)
CO
(t)
2
0.34
0.21
0.34
0.21
0.34
0.21
0.40
0.25
0-50°C
0.40
0.25
0.60
0.38
Fan pressure
Switch
7-AEV
12-PV
ON: 11 bar
OFF: 7.5 bar
MIN.- MAX
Compressed
Amb
air inlet
Temperature
After
installation
In
5-50°C
5°- 65°C
High temperature
High pressure
safety thermostat
Switch
13-HT
14-HP
80°C
28 bar
SPS026 / SPS100-ES
Minimum
Compressed
section
air inlet
validated
air outlet
F.L.A.[A]
cable for
electrical
connection
220/240V
±10%
Ø [mm2]
BSPP-F
1ph/50-60Hz
3.18
3 G 1.5
5.75
1.1/2"
8.59
Air - Side Max
Working Pressure
IP
16 bar
22
14 bar
Air
Flow
m
3
/h
156
1"
192
240
312
372
480
600
Sound
pressure level
52 dB (A)
7 / 6

Publicité

Table des Matières
loading

Table des Matières