Description of the frame:
• Bytes 2 to 4: register 328, high threshold of channel B sensor
• Bytes 5 to 7: register 329, high hysteresis of channel B sensor
In the example in grey this gives:
• Bytes 2 to 4=0x7A1200=8,000,000 in decimal: register 328, the value of the high threshold for channel B is: 8,000,000 µV i.e. 8V
• Bytes 5 to 7=0x0F4240=100,000 in decimal: register 329, the value of the high hysteresis for channel B is: 1,000,000µV i.e. 1V
FR
0
1
Code
Status
0x14
Cf Status
0x14
0xA0
Description of the frame:
EN
• Bytes 2 to 4: register 330, low threshold of channel B sensor
• Bytes 5 to 7: register 331, low hysteresis of channel B sensor
In the example in grey this gives:
• Octets 2 à 4=0x2DC6C0=3 000 000 in decimal: register 330, low threshold value on channel B: 3 000 000 µV so 3V
• Octets 5 à 7=0x0F4240=1 000 000 in decimal : register 331, low hysteresis value on channel B: 1 000 000µV so 1V

4.1.3 Network configuration information frame

During the passage into operation mode (from the Park or Command Mode), the following frame (0x20) representing the network configura-
tion of the product is transmitted:
0
1
Code
Status
0x20
Cf Status
0x20
0xA0
Description of the frame:
• Byte 2: activation of the Adaptive Data Rate: ON (value = 1) or OFF (value = 0)
• Byte 3: connection mode: ABP (value = 0) or OTAA (value = 1)
In the example in grey this gives:
• Byte 2=0x01: The Adaptive Data Rate is enabled
• Byte 3=0x01: OTAA connection mode

4.1.4 Keep Alive frame

This frame (0x30) is transmitted only in the event mode at the frequency defined by register 300.
0
1
Code
Status
0x30
Cf Status
0x30
0x42
Description of the frame:
• Byte 2: Type of the sensor on channel A. Configured by the user (register 320).
• Bytes 3 to 5: Value measured on channel A.
• If the type of sensor is 0-10V: The value is expressed in µV
• If the type of sensor is 4-20mA: The value is expressed in nA
• Byte 6: Type of the sensor on channel B. Configured by the user (register 322).
• If the type of sensor is 0-10V: The value is expressed in µV
• If the type of sensor is 4-20mA: The value is expressed in nA
• Bytes 7 to 9: Value measured on channel B.
2
3
4
S330
0x2DC6C0
2
3
4
ADR
MODE
X
0x01
0x01
2
3
4
Sensor
Value read on the channel A sensor
type
0x01
0x0C3500
5
6
7
PAYLOAD
S331
0x0F4240
5
6
7
PAYLOAD
X
X
X
5
6
7
PAYLOAD
Sensor
Value read on the channel B sensor
type