Sommaire des Matières pour ADEUNIS WMBUS DRY CONTACTS
Page 1
WMBUS DRY CONTACTS Transceiver Digital Interface Guide utilisateur / User Guide Version 2.0.0 Ce Guide utilisateur s’applique à partir des versions logicielles suivantes : This User Guide applies from the following firmware versions: Version RTU : V00.04.00 Version APP : V01.03.04 adeunis ®...
Page 2
Ninguna parte de este documento puede ser reproducida o transmitida (en fotocopias electrónico o en papel, o) sin el acuerdo adeunis®. Este documento puede ser modifi cada sin previo aviso. Todas las marcas comer- ciales mencionadas en esta guía son el tema de los derechos de propiedad intelectual.
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 TABLE DES MATIERES FRANCAIS INFORMATIONS PRODUITS ET REGLEMENTAIRES PRESENTATION DU PRODUIT 1.1. Description générale 1.2. Encombrement 1.3. Carte électronique 1.4. Spécifications Techniques 1.4.1 Caractéristiques générales 1.4.2 Autonomie 1.4.3 Caractéristiques des interfaces physiques FONCTIONNEMENT DU PRODUIT 2.1.
Page 4
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 ENGLISH PRODUCTS AND REGULATORY INFORMATION PRODUCT PRESENTATION 1.1. General description 1.2. Dimensions 1.3. Electronic board 1.4. Technical Specifications 1.4.1 General characteristics 1.4.2 Autonomy 1.4.3 Physical interface characteristics PRODUCT OPERATION 2.1.
Ce document et l’utilisation de toute information qu’il contient, est soumis à l’acceptation des termes et conditions adeunis®. adeunis® ne donne aucune garantie sur l’exactitude ou l’exhaustivité du contenu de ce document et se réserve le droit d’apporter des modifi cations aux spécifi cations et descriptions de produit à tout moment sans préavis.
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 Déclaration UE de Conformité Nous adeunis 283 rue LOUIS NEEL 38920 Crolles, France 04.76.92.01.62 www.adeunis.com Déclarons que la DoC est délivrée sous notre seule responsabilité et fait partie du produit suivant : Modèle produit :...
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 RECOMMANDATIONS ENVIRONNEMENTALES Tous les matériaux d’emballage superfl us ont été supprimés. Nous avons fait notre possible afi n que l’emballage soit facilement séparable en trois types de matériaux : carton (boîte), polystyrène expansible (matériel tampon) et poly- éthylène (sachets, feuille de protection en mousse).
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 RECOMMANDATIONS D’USAGE • Avant d’utiliser le système, vérifi ez si la tension d’alimentation fi gurant dans son manuel d’utilisation corres- pond à votre source. Dans la négative, consultez votre fournisseur.
NOTE IMPORTANTE : le démarrage du WMBUS DRY CONTACTS ne peut se faire que grâce à un aimant. Description : • Le WMBUS DRY CONTACTS d’adeunis® est un émetteur radio prêt à l’emploi permettant de reporter des états et des alarmes sur un réseau WMBUS.
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 2. FONCTIONNEMENT DU PRODUIT 2.1. Modes de fonctionnement NOTE IMPORTANTE : adeunis® utilise le format de données Big-Endian Le produit dispose de plusieurs modes de fonctionnement : MODE PARC Présence d’un aimant...
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 2.1.4 Mode REPLI Le produit entre dans ce mode très basse consommation suite à la détection d’un niveau de batterie trop faible. Dans ce mode le produit se réveille toutes les 5 secondes pour faire clignoter 2 fois la LED rouge.
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 2.2.2 Transmission périodique Le produit permet le comptage et la transmission périodique des évènements survenus sur les entrées selon le schéma suivant : Produit en veille Changement Période sur entrée...
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 2.2.3 Fonctionnement des compteurs Les compteurs représentent selon la configuration, le nombre de fronts hauts et bas, bas uniquement ou hauts uniquement. Ils sont codés sur 2 octets donc limités à une valeur de 65 535, l’utilisateur doit donc être vigilant sur la périodicité d’envoi afin de ne pas dépasser 65 535 évènements entre deux émissions.
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 2.2.4 Transmission d’une trame de vie journalière En mode évènementiel uniquement, le produit pourrait ne jamais envoyer de trames de données. Ainsi, pour s’assurer du bon fonctionnement de celui-ci une trame de vie est transmise régulièrement selon le schéma suivant : Produit en veille Période...
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 2.2.5 Mode TEST Ce mode permet à l’utilisateur de réaliser des essais du produit plus rapidement en réduisant les échelles de temps du mode production et en modifiant le comportement des LEDS.
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 CONFIGURATION DU PRODUIT La configuration du produit se fait au moyen du connecteur USB. Cette connexion permet de communiquer avec le produit par un port com virtuel et d’envoyer des commandes AT pour modifier les paramètres du produit.
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 3.2. Mode commande Utiliser un terminal port COM pour communiquer avec le produit. Nous utilisons le soft terminal port COM HERCULES disponible en télécharge- ment gratuit à l’adresse suivante : http://www.hw-group.com/products/hercules/index_en.html...
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 3.3. Commande AT Une commande débute avec les 2 caractères ASCII : « AT », suivis d’un ou plusieurs caractères et données (voir ci-après la syntaxe des com- mandes AT disponibles sur le modem).
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 3.4. Description des registres A la mise sous tension le produit fonctionne selon la dernière configuration sauvegardée (configuration usine si c’est la première mise sous tension, ou si cette configuration n’a pas été changée).
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 4. DESCRIPTION DES TRAMES Le produit transmet des informations brutes en provenance des capteurs en utilisant le protocole Wireless M-BUS. Vous trouverez dans ce chapitre les informations permettant de décoder la trame Wireless M-Bus ainsi que les données utiles.
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 4.2.1.02 Status byte L’octet de statut (status byte) est décomposé de la manière suivante : Alarm Status Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2...
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 • Octet 5=0x00 : registre 321 : o TOR2 désactivée o Pas de période de garde • Octet 6=0xB4 : registre 322 : o TOR3 configurée en mode évènementiel o Détection des fronts haut uniquement...
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 4.2.5 Trame de données Cette trame (0x40) contient les valeurs relevées sur les différents TOR. Code Status PAYLOAD 0x40 Cf Status Informations TOR1 Informations TOR2 Informations TOR3 Informations TOR4 Détails...
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 4.2.6 Synthèse des conditions d’envoi des trames montantes Le tableau ci-après résume les conditions d’envoi des différentes trames montantes : Code Description Scenarii d’envoi 0x10 Trames d’information sur la configuration •...
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 5. PREPARATION ET DEMARRAGE 5.1. Description des câbles Zoom sur les câbles : TOR A TOR B TOR C TOR D 5.2. Exemple de câblage en entrée L’exemple suivant montre le câblage à réaliser pour récupérer en entrée l’état ouvert ou fermé du capteur 1 :...
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 5.3. Démarrage du produit via aimant Une fois la configuration du produit effectuée et son montage finalisé, le produit est prêt à être démarré. Le démarrage s’effectue à l’aide d’un aimant que l’on appose sur la partie haute du produit (cf schéma ci-dessous). L’aimant doit être maintenu en position au minimum 6 secondes de sorte à...
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 Fermeture du boîtier : Procédure : Assurez-vous que le joint d’étanchéité est bien en place sur la semelle Clipser la carte électronique sur la semelle du boîtier. Assurer-vous que le clip de fixation est bien enclenché dans l’ergot de la carte.
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 6. INSTALLATION ET UTILISATION 6.1. Positionnement correct des émetteurs Deux règles sont primordiales pour une optimisation des portées radio. • La première consiste à positionner votre produit le plus haut possible.
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 Pour retirer celui-ci, tirer vers le bas sur le levier jusqu’à ce que les ergots de blocage soient face à une partie dégagée et retirer le levier Ergots Partie dégagée 6.2.2 Fixation par vis...
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 6.2.3 Fixation Rail-DIN Ce système, intégré au boîtier, permet de fixer le produit sur un rail standard de 35mm • Pour installer le boîtier, placer les inserts supérieurs sur le rail et abaisser le produit pour le clipser •...
Version APP : V01.03.04 DISCLAIMER This document and the use of any information contained therein, is subject to the acceptance of the adeunis® terms and conditions. They can be downloaded from www.adeunis.com. adeunis® makes no warranties based on the accuracy or completeness of the contents of this document and reserves the right to make changes to specifi...
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 EU Declaration of Conformity adeunis 283 rue LOUIS NEEL 38920 Crolles, France 04.76.92.01.62 www.adeunis.com Declare that the DoC is issued under our sole responsibility and belongs to the following product:...
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 ENVIRONMENTAL RECOMMENDATIONS All superfl uous packaging materials have been eliminated. We have done everything possible to make it easy to separate the packaging into three types of materials: cardboard (box), expanded polystyrene (fi ller material) and polyethylene (packets, foam protective sheets).
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 RECOMMANDATIONS REGARDING USE • Before using the system, check that the power supply voltage shown in the user manual corresponds to your supply. If it doesn’t, please consult your supplier.
• The use of the WMBUS protocol allows you to integrate the WMBUS DRY CONTACTS into any network that is already deployed. • Four digital inputs can be supported by a single WMBUS DRY CONTACTS transmitter.
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 1.4. Technical Specifications 1.4.1 General characteristics Parameters Value Supply voltage Nominal 3.6V Power supply: Removable battery version: SAFT LS14500 Maximum power 90mA Working temperature -25°C / +70°C Dimensions: 105 x 50 x 27mm...
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 1.4.3 Physical interface characteristics The schematic diagram of the digital input interfaces is the following: Absolute maximum values Units Minimum input current - 0,7 Maximum input current Electrical characteristics Unité...
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 2. PRODUCT OPERATION 2.1. Global operation Important: adeunis® use the most significant byte first format. The product has several operating modes: PARK MODE Presence of a magnet on the product >6s...
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 2.1.4 REPLI mode The product enters this very low consumption mode following the detection of a level of battery that is too low. In this mode the product wakes up every 5 seconds to make the red LED flash twice.
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 2.2.2 Periodic transmission The product allows the measurement and the periodic transmission of the values of the sensors according to the following diagram: Product in standby Change on Period...
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 2.2.3 Operation of the counters The counters represent, depending on the configuration, the number of high and low, low only or high only edges. They are coded on 2 bytes therefore limited to a value of 65,535 the user must therefore be vigilant on the periodicity of sending in order not to exceed 65,535 events between two transmissions.
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 2.2.4 Transmission of a daily Keep Alive frame In the event mode only, it is possible that the product would never send data frames. So to be sure that it is working properly a Keep Alive frame...
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 2.2.5 TEST Mode This mode allows the user to perform tests of the product more quickly by reducing the time scales of the production mode and modifying the behaviour of the LEDs.
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 DEVICE CONFIGURATION The device can be configured using the USB connector. This connection allows you to communicate with the device via a virtual com port and to transmit AT commands in order to modify the parameters of the device.
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 3.2. Command mode Use a COM port terminal in order to communicate with the device. We use the HERCULES COM port soft terminal available to download for free by clicking on the following link: http://www.hw-group.com/devices/hercules/index_en.html •...
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 3.3. AT Commands A command starts with 2 ASCII characters: “AT”, followed by one or more characters and data (see the list below for the syntax of AT com- mands available on the modem).
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 3.4. Description of the registers On switching on the product works according to the last saved configuration (Factory Configuration if it is the first start, or if this configuration has not been changed).
Page 58
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 Input TOR1 configuration: Hexadecimal Default : 0x46 Bits 0 to 3: Type • 0 = Disabled • 1 = Input - Periodic Mode - High edge • 2 = Input - Periodic Mode - Low edge •...
Page 59
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 Clé AES (première Hexadécimal Défaut : 0 partie – MSB) Clé codée sur 32 caractères. Chacun des 4 registres contient 8 caractères. Clé AES (deuxième Hexadécimal Exemple : partie – MID MSB) AES-KEY = 01020304050607080910111213141516 Clé...
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 4. DESCRIPTION OF THE FRAMES Le produit transmet des informations brutes en provenance des capteurs en utilisant le protocole Wireless M-BUS. Vous trouverez dans ce chapitre les informations permettant de décoder la trame Wireless M-Bus ainsi que les données utiles.
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 4.2.1.02 Status Byte The status byte is broken down in the following way: Alarm Status Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1...
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 • Byte 6=0xB4: register 322: • TOR3 configured in event mode • Detection of high edges only • Waiting period of 20 second • Byte 7=0x32: register 323: • TOR4 configured in periodic mode •...
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 4.2.5 Data Frame This frame (0x40) contains the values measured on the different digital outputs. Code Status PAYLOAD 0x40 Cf Status Informations TOR1 Informations TOR2 Informations TOR3 Informations TOR4...
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 4.2.6 Summary of the conditions of transmission of uplink frames The table below summarizes the conditions of the transmission of the different uplink frames: Code Description Scenarii d’envoi 0x10 Product configuration data frames •...
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 5. PREPARATION AND START-UP 5.1. Cable description Zoom on the cables: TOR A TOR B TOR C TOR D 5.2. Example of Input Wiring The following example shows the wiring to be performed to recover the open or closed state of the sensor 1:...
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 5.3. Starting up the product using a magnet Once the product has been configured and its assembly has been finalised, the product is ready to be started up. The start-up is carried out using a magnet which you place on the upper part of the product (cf. the diagram below). The magnet must be held in position for at least 6 seconds so as to confirm the start-up of the product.
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 5.5. Closing the casing Once previous stages have been carried out, you can close the casing of the WMBUS DRY CONTACTS Procedure: Make sure that the seal is properly positioned on the base Clip the electronic board onto the casing’s base.
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 6. INSTALLATION AND USE 6.1. Correct positioning of the product transceivers There are two key rules for optimising radio ranges. • The first one consists of positioning your product as high as possible.
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 To optimise fastening onto a tube or mast, we recommend you Pins remove the Rail-DIN locking/unlocking lever. To remove it, pull the lever down until the locking pins are opposite Freed up part a freed-up part and then remove the lever.
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 6.2.3 DIN-Rail fixing This system, integrated into the casing, enables the product to be fastened onto a standard 35 mm rail. • To fit the casing, place the upper inserts on the rail and lower the product to clip it into position.
Page 71
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 DEUTSCH Vor- schriften 71 of 75...
Recht vor, jederzeit und ohne Vorankündigung Änderungen an den Produktspezifi kationen und -beschreibungen vorzunehmen. adeunis® behält sich alle Rechte an diesem Dokument und den darin enthaltenen Informationen vor. Die Ver- vielfältigung, Nutzung oder Weiterverbreitung an Dritte ohne ausdrückliche Genehmigung ist streng untersagt.
Page 73
Programmiersprachen, unter Verwendung jeglicher elektrischer, mechanischer, magnetischer, optischer, manueller Geräte oder anderer Methoden, ist untersagt. adeunis® behält sich das Recht vor, ohne schriftliche Bekanntgabe und ohne ausdrückliches Verlangen seiner Kun- den die technischen Spezifi kationen oder Funktionen seiner Produkte zu ändern und sicherzustellen, dass die ihnen zur Verfügung gestellten Informationen gültig sind.
Page 74
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 UMWELTSCHUTZHINWEISE Es wurden alle überfl üssigen Verpackungsmaterialien vermieden. Wir haben uns bemüht, dass die Verpackung leicht in drei Materialarten getrennt werden kann: Pappe (Schachtel), expandiertes Polystyrol (Puff ermaterial) und Polyethylen (Tüten, Schaumstoff -Schutzlage). Ihr Gerät besteht aus recycelbaren Materialien, die im Falle einer Demontage durch ein Fachunternehmen wiederverwendet werden können.
WMBUS DRY CONTACTS - Guide utilisateur / User guide version V2.0.0 GEBRAUCHSHINWEISE • Überprüfen Sie vor Benutzung des Systems, ob die in dessen Betriebsanleitung angegebene Versorgungsspan- nung mit Ihrer Stromquelle übereinstimmt. Falls nicht, wenden Sie sich an Ihren Lieferanten. •...