• Byte 7: register 323, configuration of the events on channel B
• Byte 8: register 306, product mode (Park, Standard (production), Test or DEAD)
In the example in grey this gives:
• Byte 2=0x48: register 300, Keep Alive frame issued every 12 hours
• Byte 3=0x00: register 301, event mode
• Byte 4=0x02: register 320, channel A configured for a 4-20mA sensor
• Byte 5=0x03: register 321:
o Detection of high and low thresholds on channel A
o Detection of event on disabled digital input
o No waiting period
• Byte 6=0x01: register 322, channel B configured for a 0-10V sensor
• Byte 7=0x02: register 323:
o Detection of high and low thresholds only
o Detection of event disabled digital input
o No waiting period
• Byte 8=0x01: register 306, Production mode in progress
WARNING : if none of the channels is configured (value = None in registers 320 and 322), the product will send the configuration frame 0x10
periodically (period defined by register 300)
0
1
Code
Status
PAYLOAD
0x11
Cf Status
0x11
0xA0
Description of the frame:
• Bytes 2 to 4: register 324, high threshold of channel A sensor
• Bytes 5 to 7: register 325, high hysteresis of channel A sensor
In the example in grey this gives:
• Bytes 2 to 4=0x124F80=1,200,000 in decimal: register 324, the value of the high threshold for channel A is: 1,200,000x10=12,000,-
000nA i.e.12mA
• Bytes 5 to 7=0x0186A0=100,000 in decimal: register 325, the value of the high hysteresis for channel A is: 100,000x10=1,000,000nA i.e.
1mA
0
1
Code
Status
0x12
Cf Status
0x12
0xA0
Description of the frame:
• Bytes 2 to 4: register 326, low threshold of the channel A sensor
• Bytes 5 to 7: register 327, low hysteresis of the channel A sensor
In the example in grey this gives:
• Bytes 2 to 4=0x0927C0=600,000 in decimal: register 326, the value of the low threshold for channel A is: 600,000x10=6,000,000nA i.e.
6mA
• Bytes 5 to 7=0x0186A0=100,000 in decimal: register 327, the value of the low hysteresis for channel A is: 100,000x10=1,000,000nA i.e.
1mA
0
1
Code
Status
0x13
Cf Status
0x13
0xA0
2
3
4
S324
0x124F80
2
3
4
S326
0x0927C0
2
3
4
S328
0x7A1200
5
6
7
S325
0x0186A0
5
6
7
PAYLOAD
S327
0x0186A0
5
6
7
PAYLOAD
S329
0x0F4240
8
9
10