In the example in grey this gives:
•
Byte 2 : register 300, Keep Alive frame period = 72x10 = 720min ie 12h.
•
Bytes 3 and 4 : register 301, periodicity of transmission (periodic mode) = 180x20=3600s ie 1h
•
Byte 5 : register 306, product mode is PRODUCTION
•
Bytes 6 and 7 : register 320, data acquisition period for alarm = 180x20=3600s ie 1h
•
Byte 8 : register 321=0x44, Modbus link configuration is:
• Bit 0 = 0 : RS485
• Bit 1 = 0 : 1 stop bit
• Bits 2 and 3 = 01 : the parity is even
• Bits 4 to 7 = 0100 : the baudrate is of 19200
•
Byte 9 : register 322= 0xC8, configuration of supply time of the external load (slave) before the Modbus request is of 200x100=20
000 ms ie 20 secondes
4.2.3 Frame of information on the network configuration
Following reception of a downlink frame with the code 0x02 or on switching to the operating mode (from the Park or Command Mode), the
next frame (0x20) representing the network confguration of the product is transmitted:
0
1
Code
Status
0x20
Cf Status
S200
0x20
0xB2
0x18
Its size is of 4 bytes.
Description of the frame:
Byte 2 : register S200 : WMBUS channel
Byte 3 : register S201 : Frame format
In the example in grey this gives:
Byte 2 =0x18 : WMBUS channel is 24
Byte 3=0x00 : the format of the frame is B-format
4.2.4 Keep Alive frame
This frame (0x30) is transmitted only in the event mode at the frequency defined by register 300.
0
1
Code
Status
0x30
Cf Status
0x30
0xB2
Its size is of 2 bytes.
It contains only the code byte (0x30) and the status byte.
2
3
PAYLOAD
S201
0x01
FR
EN