5.4 Alarm configuration page

This page is used to enable monitoring of the clock, and to set which information will be sent as well
as the destination server. You can choose which parameter or parameters to define as alarms, and
configure them.
The information displayed is described below:
- Enable SNMP Trap checkbox: enables or disables automatic sending of error messages to the
SNMP Manager(s).
- SNMP Manager 1/2/3: IP addresses of servers to receive clock alarms. Using redundant SNMP
Managers increases the reliability of reception of alarms.
- Community: user-defined clock pool or domain. It is important to give all clocks on the network
the same Community name.
- Synchronisation failure: this parameter enables detection of synchronisation faults with the
master clock (Sigma type) or the time server (Netsilon type).
Multicast: Alarm triggered when the multicast synchronisation is absent for at least
1hour
Unicast: Alarm triggered when the unicast synchronisation is absent for 3 times the
duration of the poll (periodicity) and at least 1 hour (allowing for the NTP server
maintenance)
- Hands position control: this parameter enables detection of faults in the position of the clock
hands (absent alarm on the sweep second movement).
- Reboot: this parameter enables detection of clock reboot.
- Temperature: this parameter enables reporting of high or low temperature threshold breaches
(variable temperature range).