2.2
Intended use
The unit hydraulically balances and separates the primary
and secondary flow in the installation, in combination
with the (fully) automatic removal of air, gasses, and
(magnetic) dirt from water and water/glycol mixtures.
The unit is installed within a system. The system controls
the unit, so the unit does not operate on its own.
2.3
Operating conditions
The unit is suitable for use in systems filled with clean
water or mixtures of water and glycol up to 50%. The
unit can be used in combination with chemicals /
inhibitors approved according to local directives. Please
check that it is compatible with the materials used to
construct your installation. For more information contact
your supplier. Operation in combination with other fluids
may result in irreparable damage.
WARNING
The unit is not suitable for demineralised
water, drinking water, and dangerous or
inflammable substances.
The unit should be used within the limits of the technical
specifications as given in chapter 3. In case of doubt,
always contact the supplier.
The unit is not suited for outdoor use.
2.4
Scope of delivery
1x Unit
•
1x Drain valve
•
1x User documentation
•
1x Draining instructions label
•
4
2.5
Identification sticker
A
B
C
D
E
F
G
H
I
A
Type of the unit (article number)
B
Batch number
C
Connections
D
Pressure PS
E
Temperature TS
F
Flow (max)
G
Volume V
H
Empty weight
I
Year of manufacturing
English
SPIROCROSS
Acc. to 2014/68/EU
XC...FM
Batch no.:
Connections:
Pressure PS:
Temperature TS:
Flow (max):
Volume V:
Empty Weight:
Year of manufacturing:
Spirotech bv - The Netherlands
User manual - 1.0