MESSAGES
SELFDRIVE MODE ALERT MESSAGES (Only shown pressing the Q key)
Calibration ongoing, therefore, avoid, as far as possible, opening the cold room during the
process. For further information, see page 25.
Flashing with temperature: Configuration has been changed from 1 to 2 evaporators or vice
versa.
Defrost end error in 1/2 evaporator during the calibration, defrost has not ended due to
temperature.
Error during calibration in 1/2 evaporator. There is not enough difference in temperature
between the cold room probe and the evaporator probe.
It has not been possible to carry out the calibration due to a lack of stability in the system
(Excessive door opening, excessive oscillations in the lower pressure, etc.).
Error during normal operation (SELFDRIVE Mode active) in 1/2 evaporator. There is not enough
difference in temperature between the cold room probe and the evaporator probe.
A lack of stability has been detected in the system (Excessive door opening, excessive oscillations in
the low pressure, etc.) during normal operation (SELFDRIVE Mode active).
The persistent lack of stability has led to the deactivation of the SELFDRIVE mode.
Excessive door openings have been detected during calibration and it has not been possible to
calibrate.
Excessive door openings have been detected and the device cannot regulate in SELFDRIVE mode.