Keypad
Pressing it for 3 seconds activates/deactivates the Stand-By mode. In this mode, regulation is paused and
the m icon is displayed.
In the programming menu, it exits the parameter without saving changes, returns to the previous level or
exits programming.
Pressing once without holding displays the temperature of probe S2 for 2 seconds (if it is enabled).
Pressing it for 3 seconds starts/stops the defrost.
In the programming menu, it allows scrolling through the different levels, or during the setting of a
parameter, changing its value.
A brief press shows the SELFDRIVE mode operating alerts.
Pressing it for 3 seconds activates/deactivates the continuous cycle mode.
In the programming menu, it allows scrolling through the different levels, or during the setting of a
parameter, changing its value.
Pressing once without holding activates/deactivates the cold room light.
Pressing it for 3 seconds accesses the condensed programming menu.
Pressing it for 6 seconds accesses the expanded programming menu.
In the programming menu, it accesses the level shown on the display or, during the setting of a parameter,
accepts the new value.
Pressing once without holding displays the current effective value of the Set Point, taking into
consideration temporary modifications by other parameters (C10 or C12).
When an alarm is in progress, pressing once without holding mutes the acoustic alarm.
Pressing for 3 seconds accesses the Set Point setting.
STAND-BY
If the regulation cannot be instantly stopped due to its configuration, a controlled stop process starts
and the m icon flashes. To stop the controlled stop process and force the step to Stand-by, press the
Stand-by key again for 3 seconds.
20