Parameters
Regulation and control
Description
SP
Temperature setting (Set Point)
RE
CE
SELFDRIVE Mode 0=Deactivated 1= Activated
C0
Probes 1 & 2 calibration (Offset)
C1
Probe 1 differential (Hysteresis)
C2
Set Point top locking (it cannot be set above this value)
C3
Set Point bottom locking (it cannot be set below this value)
Type of delay for the protection of the compressor:
C4
0=Minimum time of compressor in OFF
1=Minimum time of compressor in OFF and in ON in each cycle
C5
Protection delay time (Value of the option selected in parameter C4)
COOL relay status with fault in probe 1:
C6
0=OFF; 1=ON; 2=Average according to last 24h prior to probe error
3=ON-OFF according to prog. C7 and C8
Relay time in ON in the event of probe 1 failure
C7
(If C7=0 and C8¹0, the relay will always be disconnected in OFF)
Relay time in OFF in the event of probe 1 failure
C8
(If C8=0 and C7¹0, the relay will always be connected in ON)
C9
Maximum duration of the continuous cycle mode. (0=deactivated)
Variation of the Set Point (SP) in continuous cycle mode. When it reaches this
C10
point (SP+C10), it reverts to the normal mode. (SP+C10 ³ C3).
The value of this parameter is always negative, unless it is 0. (0=OFF)
Variation of the Set Point (SP) when the change Set Point function is active.
C12
(SP+C12£ C2) (0= deactivated)
Maximum start time from Pump Down
C19
(Values between 1 and 9 seconds will not be accepted) (0=deactivated)
C20
Maximum time for pump down (0= deactivated)
Probe to be displayed 0=All probes (sequential)
C21
1=Probe 1 (Chamber) 2=Probe 2 (Evaporator)
4=Weighted temperature of the cold room
C22
Stop fans and compressor on opening door 0=No 1=Yes
C23
Start-up delay for fans and compressor with door open
C24
Delay time of cold stop with door open.
C25
Influence of probe S3 when regulating with two temperature probes (I20=10)
C27
Probe 3 calibration (Offset)
EP
Exit to level 1
3=Probe 3 (According to I20)
28
1652H4A11 Ed.08
Values Min.
Def. Max.
ºC/ºF
-50
0.0
99
0
1
ºC/ºF
-4.0
0.0
4.0
ºC/ºF
0.1
2.0
20.0
ºC/ºF
C3
99
99
ºC/ºF
-50
-50
C2
0
0
Min.
0
0
120
0
2
Min.
0
10
120
Min.
0
5
120
H.
0
0
48
ºC/ºF
0
-50
C3-SP
ºC/ºF
C3-SP
0.0
C2-SP
Sec.
0
0
120
Min.
0
0
15
0
1
0
0
Min.
0
0
999
Seg.
0
0
C23
%
0
0
95
ºC/ºF
-4.0
0.0
4.0
1
1
3
3
1