Télécharger Imprimer la page

baltur LCM 100 Guide Rapide page 25

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 57
9.1.12 DIP SWITCH
With the aid of DIP switches, you can configure all the settings of
LCM100.
1
0
Functions of the DIP switches
By using DIP switch 1, you can activate or deactivate the CAN
terminating resistor.
DIP switch 1
0
CAN terminal resistence inactive
1
CAN terminal resistance active
By using DIP switches 2 - 3, you can set the LSB Family.
DIP switch 2
DIP switch 3
0
0
1
1
By using DIP switches 4 - 6, you can set the sensor inputs.
DIP
DIP
DIP
switch 4
switch 5
switch 6
0
X
X
1
X
X
X
0
X
X
1
X
X
X
0
X
X
1
LSB Family
0
1
1
2
0
3
1
4
Input
PT100 Boiler temperature sensor
PT1000 Boiler temperature sensor
PT100 Ambient temperature sensor
PT1000 Ambient temperature sensor
PT100 Flue gas temperature sensor
PT1000 Flue gas temperature sensor
0006081547_201210
9.1.13 LEDS
The LCM100 has thre LEDs which should be connected as
mentioned by the following:
LED
Colour
ERR (LED 1)
red
During normal operation, the LED is
switched off. It will light up under the
following conditions:
- Initialisation not ready or not
- Cannot receive any messages
CAN (LED 2) green OFF: CAN Controller in Bus-Off. No
communications possible.
Blinking: CAN Controller discovered a
temporary fault. After fixing the problem,
the LED would still blink for some time.
ON: CAN is ready to operate.
PWR (LED 3) green ON: Module is working normally = fully
initialised and without any fault.
5 / 18
Relevance
successfully come to an end (e.g.
HW could not be initialised)
for at least 3 seconds

Publicité

loading