Measuring output
Output signals A1 and A2
The output signals can be either load-independent DC cur-
rents I
or DC voltages U
A
A
switches and the setting range is programmed on a PC. A1
and A2 are not DC isolated and the same value is available
at both outputs.
Standard ranges for I
: 0...20 mA or 4...20 mA
A
External resistance I
: R
A1
resp. =
I
AN
lue
External resistance I
: R
A2
Standard ranges
for U
:
0...5, 1...5, 0...10 or 2...10 V
A
Load capacity
U
/ U
:
R
A1
A2
Power supply H
AC/DC power pack (DC and 45...400 Hz)
Table 2: Rated voltages and tolerances
Rated voltage
Fuse
U
N
24... 60 V
T 250 mA
DC / AC
85...230 V
1
T 100 mA
DC / AC
24... 60 V
T 160 mA
DC / AC
85...230 V
T 80 mA ± 15%
AC
85...110 V
T 80 mA – 15...+ 10%
DC
Power consumption: < 1.4 W resp. < 2.7 VA
Output contact K
The output contact can be used:
a)
as an additional means of signalling operation of the
open-circuit sensor supervision when the transmitter
is used in conjunction with resistance thermometers,
thermo-couples, resistance sensors and potentio-
meters.
b)
to monitor the measured variable in relation to a limit
or its rate-of-change where an additional means of
signalling operation of the open-circuit sensor super-
vision (see "a") is considered unnecessary.
c)
to monitor the measured variable in relation to a limit
or its rate-of-change when measuring a DC voltage
or a current.
Note on a): The relay has to be activated by programming
its operating mode as "energised" or "de-ener-
gised".
Available operating modes are:
"Output at last value, relay energised"
"Output at last value, relay de-energised"
"Output at setting, relay energised"
"Output at setting, relay de-energised"
24
. The desired mode is set on DIP
15 V
max. [kΩ] =
ext
I
[mA]
AN
– 12 V
I
[mA]
AN
= Full-scale output current va-
0.3 V
max. [kΩ] =
ext
I
[mA]
AN
U
[V]
A
[kΩ] ≥
20 mA
ext
Tolerances
Instrument
version
DC – 15...+ 33%
Standard
AC ±15%
(Non-Ex)
DC – 15...+ 33%
Type of
AC ± 15%
protection
intrinsically
safety
[EEx ia] IIC
Relay pick-up/reset threshold:
1 to 15 kΩ, acc. to measuring mode and range
Note on b): The relay must be activated by programming:
"Output corr. to input variable, relay inactive"
The limit must also be programmed (see Section
"Limit")
Note on c): It is only necessary to program the limit (see
remarks on "b)" above)
Limit value GW
Limit value type:
Programmable
– for monitoring the input variable
– for monitoring the rate-of-change
Hysteresis:
Programmable from
0.5 to 100%
resp.
1 to 100%/s
Operating and
resetting delays:
Programmable from
1 to 60 s
Input variable
limit
Lower
Upper
S
G
GW
H
H
GW
S
G
H hysteresis, GW limit value, G operation area, S failure area
Fig. 3. Switching function according to limit monitored.
Light emitting diodes
(
Table 3: Red LED (
,
Operating modes
(
(
Open-circuit sensor
or lead
Above or below limit
3
1
Caution! Observe note in Section 7.3.
In relation to analogue output spans A1 resp. A2.
2
Only applies when the output contact K is used for monitoring the
3
input variable in relation to a limit.
in relation to a lower or upper limit
between – 10 and +110%
2
side of Fig. 3)
or
of the input variable
∆ measured variable
Slope =
∆ t
between ± 1 and ± 50%/s
right side of Fig. 3)
2
2
Rate-of-change
of input variable
Slope
S
H
G
(
, Fig. 2)
Red LED
lit
lit /not lit
(acc. to programming)
(see left
(see
2
Time