TECHNICAL DATA

MODEL
TYPE
OUTPUT
(1)
FUEL
- Net calorific value
- Absolute density
- Max. delivery
- Pressure at max. delivery
(2)
OPERATION
STANDARD APPLICATIONS
AMBIENT TEMPERATUR
COMBUSTION AIR TEMPERATURE
ELECTRICAL SUPPLY
ELECTRIC MOTOR
IGNITION TRANSFORMER
ELECTRICAL POWER CONSUMPTION
ELECTRICAL PROTECTION
IN CONFORMITY WITH DIRECTIVES
Noise levels
Sound pressure
(3)
Sound power
(1) Reference conditions: Ambient temperature 20°C - Barometric pressure 1000 mbar - Altitude 100 m s.l.m.
(2) Pressure at test point 16)(A)p.8, with zero pressure in the combustion chambre, with open gas ring 2)(B)p.16 an maximum burner output
(2) Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum rated output. The
sound power is measured with the "Free Field" method, as per EN 15036, and according to an "Accuracy: Category 3" measuring accuracy,
as set out in EN ISO 3746.
COUNTRY
SE - FI - AT - GR - DK -ES - GB - IT - IE - PT - IS - CH - NO

VARIANTS

Burner model
RS 120/M BLU

ACCESSORIES

(optional):
RADIO DISTURBANCEPROTECTION KIT code 3010386.
If the burner is installed in places particularly subject to radio disturbance (emission of signals exceeding 10 V/m) owing to the presence of an
INVERTER, or in applications where the length of the thermostat connections exceeds 20 metres, a protection kit is available as an interface
between the control box and the burner.
OUTPUT POWER REGULATOR KIT: Under modulating operation, the burner automatically adapts to one of an infinite number of firing rates
between the low and high flame output position, thus ensuring stable operating conditions in terms of temperature or pressure. Two components
should be ordered: • Power regulator to install to the burner; • probe to install to the boiler.
PARAMETER TO BE CHECKED
Temperature
Pressure
KIT INTERFACE ADAPTER RMG TO PC code 3002719;
TUBES KIT code 3010248;
GAS TRAIN ACCORDING TO REGULATION EN 676 (with valves, pressure governor and filter): see page 18.
Important: The installer is responsible for the addition of any safety device not foreseen in the present manual.
MAX.
kW
Mcal/h
MIN.
kW
Mcal/h
NATURAL GAS: G20 - G21 - G22 - G23 - G25
3
kWh/Nm
3
Mcal/Nm
3
kg/Nm
3
Nm
/h
mbar
• On-Off (1 stop min each 24 hours).
• Progressive two-stage or modulating by kit (see ACCESSOIRES).
Boilers: water, steam, diathermic oil
°C
0 - 40
°C max
60
V
3 / N / PE 380 - 220 +/- 10%
Hz
60 - three-phase
rpm
W
V
A
V1 - V2
I1 - I2
W max
IP 44
2006/42/CE - 2014/35/EU - 2014/30/EU
dBA
DE
NL
FR
BE
LU
Burner code
20009506
Range
- 100...+ 500°C
0...2,5 bar
0...16 bar
RS 120/M BLU
847 T80
600 - 1300
516 - 1118
300
258
G20
10
8,6
0,71
130
22,5
3400
2200
220/380 - 440
7.3 / 4.2-4.3
230 V - 1 x 8 kV
1 A - 20 mA
2600
78,5
89,5
CATEGORY
I2L - I2E - I2 (43.46 - 45.3 MJ/m3 (0°C))
Blast tube lenght mm
390
PROBE
Type
Code
PT 100
3010110
Output probe
3010213
4...20 mA
3010214
6
G25
8,6
7,4
0,78
151
33,3
I
2H
I
2ELL
I
2Er
I
2E(R)B
I
2E
POWER REGULATOR
Type
RWF50
20082208
RWF55
20099657
GB
Code