3.10
e
xemple De connexion
Figure 40
Exemple de connexion pour quatre charges monophasées, ligne monophasée L1-L2/N
Configuration des commutateurs
Dip 1
Dip 2
Dip 3
OFF
OFF
OFF
- FIRING MODE: ZC, BF, HSC, PA
- HB DIAGNOSTIC AVAILABLE: Partial and total load failure of each single leg
FAST FUSE needed only for controller without option "F"
See table Fuse/Fuseholders
NOTE: Take care about the "F4/N" connection (see the picture)
The wire "F4/N" is required always (also if Load 4 is not used)
Figure 41
Exemple de connexion pour quatre charges monophasées, ligne triphasée sans neutre
Configuration des commutateurs
Dip 1
Dip 2
Dip 3
OFF
OFF
OFF
- FIRING MODE: ZC, BF, HSC, PA
- HB DIAGNOSTIC AVAILABLE: Partial and total load failure of each single leg
FAST FUSE needed only for controller without option "F"
See table Fuse/Fuseholders
NOTE: Take care about the "F4/N" connection (see the picture)
The wire "F4/N" is required always (also if Load 4 is not used)
80404I_MHW_GFX4-IR_10-2019_FRA
:
section De puissance
Dip 4
Dip 5
OFF
OFF
Dip 4
Dip 5
OFF
OFF
P
Id = ___
V cosj
V =
tension de phase (ligne L1 - ligne L2/N)
P =
puissance de chaque charge monophasée
Id =
courant dans la charge
si charge résistive cosj = 1
P
Id = ___
V cosj
V =
tension de phase (ligne L1 - ligne L2/N)
P =
puissance de chaque charge monophasée
Id =
courant dans la charge
si charge résistive cosj = 1
31