3.4
Operating conditions
The Access Control may only be operated under the following operating conditions:
Operating condition
Temperature operational range
Humidity operational range
Degree of protection
4
Assembly
4.1
Assembly instructions
The assembly of the Access Control is made as shown in fig. 2.
◾ Mount the Access Control so that the front with the transmitter and receiver is pointing to the
monitored door.
◾ Stick the enclosed reflective foil on the door and the side wall exactly opposite of the IR sensor.
Note:
The distance between the IR sensor in the Access Control and the reflective foil must
not exceed 10 cm. Please reposition the Access Control accordingly, if necessary.
5
Installation and operation
5.1
Operating and display elements
The operating and display elements are shown in fig. 5.
Key for fig. 5
1
Infrared receiver
2
Infrared diode (transmitter)
3
Multi-LED for the status display
4
CAN bus connection, 24 V
5
CAN bus connection, 24 V
6
Connection for handle RJ 12
7
Connection for the CMC III reader unit
5.2
Installation
Note:
The CMC III Processing Unit or Processing Unit Compact must contain the software
version ≥ V 3.15.80. This means that the Access Control DK 7030.202 automatically
receives the necessary software update via the PU. This is the only way to guarantee
the function of the unit.
◾ If required, connect the following connection accessory to the appropriate connection (fig. 5,
pos. 6, 7).
– CMC III coded lock VX (DK 7030.222, DK 7030.223)
– CMC III transponder reader unit VX (DK 7030.232, DK 7030.233)
– CMC III online comfort handle VX (DK 7030.610, DK 7030.611)
– CMC III online adaptor for radio comfort handle VX (DK 7030.624)
Rittal CMC III Access Control
Product description, Assembly, Installation and operation
CMC III Access Control
0 °C to +55 °C
5% to 95% relative humidity, non-condensing
IP 30 in accordance with IEC 60 529
EN