Télécharger Imprimer la page

Rittal CMC III Notice D'installation Et D'utilisation page 10

Publicité

Les langues disponibles

Les langues disponibles

Installation and operation, Service
– Electromagnetic Ergoform-S handle (DK 7320.700)
– Electromagnetic TS 8 handle with master key function with and without CCP (DK 7320.721)
EN
◾ Connect the Access Control with a CAN bus connection cable to the CMC III PU, the PU Compact
or to the neighbouring elements on the CAN bus (fig. 5, pos. 4, 5).
Display of the status change:
– With the CMC III Access Control, the two green and two red CAN bus LEDs on the CAN bus
connection will flash during the initialisation process. Once initialisation is complete, only the
green LEDs will be illuminated.
– The multi-LED of the Processing Unit flashes continually in the green – orange – red sequence.
– The multi-LED of the Access Control flashes blue continuously.
◾ Press the "C" key on the CMC III PU or the PU Compact (a first audio signal is issued) and keep it
pressed for approx. 3 seconds until a second audio signal is issued.
Display of the status change on the CAN bus LEDs:
– Green LEDs light continuously: CAN bus status "OK".
– Red LEDs light continuously: CAN bus status faulty.
Display of the status change on the multi-LED of the Processing Unit.
– Continuous green light: All units attached to the CAN bus have the "OK" status.
– Continuous orange light: At least one unit attached to the CAN bus has the "warning" status.
– Continuous red light: At least one unit attached to the CAN bus has the "alarm" status.
Display of the status change on the multi-LED of the Access Control:
– Continuous blue flashing: Communication over the CAN bus.
– Green flashing: When the measured value changes or, at the latest, every 5 seconds.
– Continuous red flashing: The Access Control has the "open" status.
– Continuous red light: Invalid measured value.
If the installation is not successful: see section 1.1.
Note:
Connection cables in various lengths can be obtained from Rittal.
5.3
Settings
The following parameters can be set or viewed at the CMC III PU or PU Compact web site:
– Value: The current value of the access sensor (0 = door closed, 1 = door open)
– Sensitivity: Distance of sensor from door (1=small, 3=large)
– Delay: Status message delay [s]
– Status: Current status of the access sensor taking account of the delay value
Similarly, the parameters of the connected accessory can be set from the CMC III PU or PU Compact
web site (see section 1.1).
To determine whether any software updates are required: see www.rittal.com or contact
Rittal Service (see section 6).
6
Service
For technical questions, please contact:
Tel.: +49(0)2772 505-9052
E-mail: info@rittal.de
Homepage: www.rittal.com
For complaints or service requests, please contact:
Tel.: +49(0)2772 505-1855
E-Mail: service@rittal.de
10
Rittal CMC III Access Control

Publicité

loading

Ce manuel est également adapté pour:

Dk 7030.202