LOCK: indicate UPS or a UPS component lock and usually is preceded by an alarm signal. In the event of a fault and
consequential inverter lock, the inverter and power to the load via the bypass line will switch off (this procedure is
excluded for locks due to serious, persistent overloads and short circuits).
CODE
L01
L02
L03
L04
L05
L06
L07
L08
L09
L10
L11
L12
L13
L14
L15
L16
L17
L18
L19
L20
L21
L22
L23
L24
L25
L26
L27
L28
L29
//
L32
//
L33
L30
L31
L34
L35
L36
L37
L38
L39
L40
L41
L42
L43
L44
//
L45
//
L46
//
L47
//
L48
// = Parallel Lock
IV332 Rev.001 SIEL S.p.A.
Data di emissione: 2012-06-04
DESCRIPTION
Incorrect auxiliary power supply
Disconnection of one or more internal cables
Phase1 input fuse broken or input contactor locked (does not close)
Phase2 input fuse broken or input contactor locked (does not close)
Phase3 input fuse broken or input contactor locked (does not close)
Positive BOOST stage overvoltage
Negative BOOST stage overvoltage
Positive BOOST stage undervoltage
Negative BOOST stage undervoltage
Static bypass switch fault
L1 bypass output locked
L2 bypass output locked
L3 bypass output locked
Phase1 inverter overvoltage
Phase2 inverter overvoltage
Phase3 inverter overvoltage
Phase1 inverter undervoltage
Phase2 inverter undervoltage
Phase3 inverter undervoltage
Continuous voltage on inverter output or Phase1 sinusoid inverter deformed
Continuous voltage on inverter output or Phase2 sinusoid inverter deformed
Continuous voltage on inverter output or Phase3 sinusoid inverter deformed
Phase1 output overload
Phase2 output overload
Phase3 output overload
Phase1 output short-circuit
Phase2 output short-circuit
Phase3 output short-circuit
Phase1 output fuse broken or output contactor locked (does not close)
Parallel synchronization error
Parallel synchronization signal fault
Phase2 output fuse broken or output contactor locked (does not close)
Phase3 output fuse broken or output contactor locked (does not close)
Phase1 dissipator overtemperature
Phase2 dissipator overtemperature
Phase3 dissipator overtemperature
Battery charger overtemperature
Phase1 dissipator temperature sensor fault
Phase2 dissipator temperature sensor fault
Phase3 dissipator temperature sensor fault
Battery charger temperature sensor fault
BOOST 1 battery fuse broken
BOOST 2 battery fuse broken
BOOST 3 battery fuse broken
Parallel bus separation
Parallel communication fault
Parallel board fault
Remote unit lock