LECTROMAGNETIC COMPATIBILITY
This UPS complies with applicable EMC (Category C3).
ATTENTION:
This product is designed for second environment* commercial and industrial applications - it may be necessary during
installation to introduce certain restrictions and take additional measures to prevent disturbances.
Connection to USB and RS232 connectors must be made with the supplied cables or, however, with shielded cables that are no
longer than 3 metres.
(*) Type of environment defined in EMC regulations
I
NSTALLATION ENVIRONMENT
When selecting the installation site of the UPS and any Battery Boxes, observe the following notes:
avoid dusty environments
ensure that flooring is flat and able to sustain the weight of the UPS (and Battery Boxes)
avoid environments that are too narrow which might prevent normal maintenance operations
relative humidity must not exceed 90%, without condensation
verify that the room temperature, with the UPS in operation, is maintained between 0 and 40°C
The UPS is able to operate at a temperature between 0 and 40°C. The recommended operating
temperature for the UPS and the batteries is between 20 and 25°C. The actual operating life of the batteries
is 5 years on average at an operating temperature of 20°C. If the operating temperature reaches 30°C, the
operating life is halved.
avoid positioning the UPS in places which are exposed to direct sunlight or to hot air
To maintain installation room temperature in the above indicated range, waste heat disposal should be provided for (the value of
kW/kcal/h/ B.T.U /h dissipated by the UPS is shown in the table on the previous page). Methods which can be used include:
natural ventilation
forced ventilation, recommended if the external temperature is lower (e.g. 20°C) than the temperature at which you
want to operate the UPS and/or the Battery Box (e.g. 25°C)
air conditioning system, recommended if the external temperature is higher (e.g. 30°C) than the temperature at which
you want to operate the UPS and/or the Battery Box (e.g. 25°C)
IV332 Rev.001 SIEL S.p.A.
Data di emissione: 2012-06-04
Pag. 70 di 272 + FR