C
ONNECTIONS TO
Follow the instructions below in order:
open the door
remove the terminal cover panel positioned under the switches (see "Front UPS views" )
connect the protective conductor (ground cable) to the PE marked screw.
connect the input, output and battery cables to the terminal board, observing the positions and polarities indicated in
the figure below
Note: connection of the protective conductor (ground cable ) must be made through an eyelet terminal with an M6 screw
Once installation operations have been completed and connections verified (see paragraph "First start-up and initial settings"),
restore the terminal cover panel and close the door.
C
ONNECTIONS TO
Follow the instructions below in order:
open the door
remove the terminal cover panel positioned under the switches (see "Front UPS views" )
connect the protective conductor (ground cable) to the PE marked screw.
connect the input, bypass, output and battery cables to the terminal board, observing the positions and polarities
indicated in the figure below
Note: connection of the protective conductor (ground cable ) must be made through an eyelet terminal with an M6 screw
The input and bypass Neutral must always be connected.
The input and bypass lines must be connected to the same potential as of the Neutral.
Once installation operations have been completed and connections verified (see paragraph "First start-up and initial settings"),
restore the terminal cover panel and close the door.
IV332 Rev.001 SIEL S.p.A.
Data di emissione: 2012-06-04
S
E
-HF 60-80
AFEPOWER
VO
S
E
-HF 60-80
AFEPOWER
VO
MODELS WITH STANDARD BYPASS
MODELS WITH SEPARATE BYPASS
Pag. 75 di 272 + FR