99638481_A_ML.qxp
08/12/2005
I
nstalling your hood ?
If you possess an outlet to the exterior: fig. 4
Your hood can be connected to this using a flue (minimum Ø 125 mm, enamelled, made from
aluminium, flexible or made from a non-flammable material). If your flue is below 125 mm in
diameter, you must obligatorily use the "recycling" mode.
If you do not possess an outlet to the exterior: fig. 5
All of our appliances can be used in recycling mode.
In this case, you should add an active carbon filter which will keep in odours.
A
ssembling your hood
The hood must be installed in conformity with the applicable regulations
concerning the ventilation of premises. In France, these regulations are
detailed in DTU 61.1 from the CSTB. In particular, the evacuated air must not
be channelled into a duct used to evacuate fumes from appliances using gas or
other combustible fuels. Disused ducts may only be used after approval from a
competent specialist.
The minimum distance between the cooking surface and the lowest part of the
hood must be 70 cm. If the instructions for the hob installed under the hood
specify a distance of more than 70 cm, this requirement must be respected.
- Draw a horizontal line 70 cm minimum from the cooktop.
- Draw a vertical line on the wall running from the ceiling to the lower edge of the hood.
- Place the mounting hole template against the wall (fig. 2)
- Drill the 6 holes. Insert the 6 wall plugs.
- Screw up the top two screws of the hood, but not completely - allow them to
protrude by 5 mm
- Remove the metal filter.
- Attach the suction hood to the two screws (fig. 3).
- Screw up the two screws at the bottom.
Adjust the level of your hood before fully tightening up all four screws.
C
onnecting up your hood
This appliance is delivered with a H 05 VVF power cable with three
conductors of 0.75 mm2 (neutral, live and earth).
connected to the 220-240 V single phase mains network via a CEI 60083
standard plug which must remain accessible following installation, or an all
pole cut-off device with a minimum contact opening distance of 3 mm. We will
not be liable in the event of an accident arising following incorrect or
non-existent earthing. The fuse for your installation must be 10 or 16A. If the
power cable is damaged, call the after sales service department in order to
avoid danger.
16:30
Page 14
(fig. 3)
.
.
This must be