Motor Overtemperature Protection:
These drive models are not provided with load and speed sensitive overload protection
and thermal memory retention up on shutdown or loss of power (for details see NEC,
article 430.126(A)(2)".
Branch Circuit Protection
Information about the required Branch Circuit Protection which need to be installed
external to the product: see Table 1
For Type E combination motor controllers, the marking shall include the motor controller
manufacturer, model number,rated voltage and rated hp: see Table 2 or 3
Cat.
No.
05B6
05B6
07B6
07B6
09B6
"The Voltage Rating of the external Fuse(s) shall be at least equal to the input
1)
voltage of the Inverter Module" (or similar wording)
Table 1: External Branch Circuit Protection of inverter modules
Listed (NKJH) Type E Self Protected Manual Motor Controllers.
Type and manufacturer and electrical ratings as specified below:
Cat.
No.
05B6
05B6
07B6
07B6
09B6
all Drives series which use a Self Protected Motor Controller rated 480Y/277V are
1)
suitable for 480Y/277V sources only.
Table 2: External Branch Circuit Protection of inverter modules
F - 40
Input Voltage
120 V / 1ph
240 V / 1ph
240 V / 1ph
480 V / 3ph
480 V / 3ph
Drive Input
Self Protected Manual Motor Control-
rating
ler Type and manufacturer
1)
120 V / 1ph
PKZMO–10E, Eaton Industries
240 V / 1ph
PKZMO–10E, Eaton Industries
240 V / 1ph
PKZMO–10E, Eaton Industries
480 V / 3ph
PKZMO–10E, Eaton Industries
480 V / 3ph
PKZMO–10E, Eaton Industries
UL248
Fuse type CC, J,RK5 maximum rating
10 A
6 A
10 A
6 A
10 A
1)
Self Protected Manual
Motor Controller rating
115 V, 0.5 hp
230 V/ 1ph, 1.5 hp
230 V/ 1ph, 1.5 hp
480Y/277V, 7.5 hp
480Y/277V, 7.5 hp

Publicité