An integrated collective fault signal is applied at the SSM terminals
as a potential-free changeover contact.
Contact load:
ƒ
Permitted minimum: SELV 12 V AC / DC, 10 mA
ƒ
Permitted maximum: 250 V AC, 1 A, AC1 / 30 V DC, 1 A
6.8
Collective run signal (SBM) – orange terminal block
➜ Fig. 23
An integrated collective run signal is applied at the SBM terminals as
a potential-free normally open contact. Contact load:
ƒ
Permitted minimum: SELV 12 V AC / DC, 10 mA
ƒ
Permitted maximum: 250 V AC, 1 A, AC1 / 30 V DC, 1 A
6.9
Connecting and removing the Wilo-Connector
WARNING
Risk of fatal electrical shock!
ƒ
Never connect or remove live plugs!
Connect
➜ Fig. 15 to 20
Spring clips: WAGO "Cage Clamp".
Remove
➜ Fig. 21
ƒ
Remove the Wilo-Connector only using a suitable tool!
Installation and operating instructions Wilo-Stratos MAXO/-D/-Z
6.10
Bluetooth radio interface
The pump has a Bluetooth interface for connecting to mobile
devices. Using the Wilo-Smart Connect app and a smartphone, you
can operate and adjust the pump and read out pump data.
Bluetooth is active by factory default and can, if required, be deac-
tivated via the Settings/Device settings/Bluetooth menu.
ƒ
Frequency band: 2400 MHz – 2483.5 MHz
ƒ
Maximum radiated transmission power: < 10 dBm (EIRP)
7
Put into operation
7.1
Venting
1. Fill and vent the system correctly.
To vent the rotor chamber if required, activate the pump venting
function in the pump menu.
7.2
Pump operation
Description of operating elements
➜ Fig. 3 and 4
Pos. Name
Explanation
Graphic dis-
Provides information about settings and
play
pump status.
3.1
Self-explanatory user interface for setting
the pump.
Green LED in-
LED lights up, pump supplied with power.
3.2
dicator
There are no warnings and no faults.
en