IV - What to do if...? ... Check.
What to do if...?
No broadcasting sounders
No DHCP server on the
network
Harmonys does not
broadcast any sound
The sounder emits a
continuous beep
26
1) The multicast address is identical between the master clock
and Harmonys.
2) Network parameters are compatible: Harmonys must be on
the same Ethernet network as the computer with the Sigma
software.
1) By default the Harmonys takes on the following IP setting
(after 3min):
- IP: 192.192.223.100 (1st sounder), 192.192.222.101 (2nd
sounder), etc.
- MASK: 255.255.0.0
- Gateway: 0.0.0.0
- DNS: 0.0.0.0
(After 15 minutes, the sounder asks an address DHCP server).
2) Using the Sigma software (Configuration> IP devices>
Network button) to set the network settings Harmonys
(product identification with the MAC address on the tag on
the back of the product).
1) The maximal power of the switch PoE is sufficient to feed all
the products connected to the switch.
2) The length of the cable is lower than 100 meters (refer to the
standards of network cabling).
3) The power output of the switch is sufficient (IEEE 802.3af) to
power the product.
4) Harmonys sounder is on the broadcast area of the master
clock Sigma.
5) The sounder volume is high enough in the programming of
the web server (see page 18). The sounder beeps when
pressing the test button.
6) The multicast address is identical between the master clock
and Harmonys.
1) Sounders in repeater mode (client or server) are:
- properly connected.
- set to the same IP address.
... Check