Output functions
Switching function:
output 1 / 2 switching PNP; function
can be set separately per output
Analogue output:
only output 2
Electrical connection
The unit must only be connected by a skilled electrician. The
national and international regulations for the installation of elec-
trical equipment must be adhered to.
Voltage supply to EN50178, SELV, PELV.
Disconnect power before connecting the unit.
BN
1
+
BK
4
S1
WH
2
S2
3
BU
NOTE: If output 2 is connected to an analogue input card, the para-
meters of the output must be set first (OU2 = I or OU2 = U).
Otherwise the input card can be destroyed.
Core colours:
1 = BN (brown)
2 = WH (white)
3 = BU (blue)
4 = BK (black)
pnp pnp
Output 1
hysteresis function / N.O. (Hno)
hysteresis function / N.C. (Hnc)
window function / N.O. (Fno)
window function / N.C. (Fnc)
—
Output 2
I: 4 ... 20 mA
U: 0 ... 10 V
23