7. Safety-related instructions / 8. Faults
Temperature class classification, ambient temperatures
A heating in the connection head can occur with built-in transmitter through faulty
electronics. The permissible ambient temperatures depend on the cases used and any
EN
additionally fitted head-mounted transmitter.
For all WIKA connection heads with built-in WIKA temperature transmitters, the
following interrelation is valid:
The temperature increase on the surface of the connection head or case is less than 25 K
if the following conditions are observed: supply voltage U
transmitter is operated in a current limit of 22.5 mA.
The temperature class is dependent upon the user application and the ambient temperature.
The permissible ambient temperatures for third-party products can be seen from the relevant
approvals and/or data sheets. However, an impermissible heat reflux from the process
which can exceed the operating temperature of the case or the temperature class, must be
prevented through suitable heat insulation or a suitably long neck tube.

8. Faults

DANGER!
Danger to life from explosion
Through working in flammable atmospheres, there is a risk of explosion which
can cause death.
CAUTION!
Physical injuries and damage to property and the environment
If faults cannot be eliminated by means of the listed measures, the instrument
must be taken out of operation immediately.
For contact details, please see chapter 1 "General information" or the back
page of the operating instructions.
16
Only rectify faults in non-flammable atmospheres!
Ensure that there is no longer any signal present and protect against being
put into operation accidentally.
Contact the manufacturer.
If a return is needed, please follow the instructions given in chapter 10.2
"Return".