FCX APC - VENTILCONVETTORE CON DEPURATORE D'ARIA PLASMACLUSTER
FCX APC - USE
CONTROLS:
The "PLASMACLUSTER" purifier cuts in automatically when the ventilation comes on.
ON / OFF
OFF
The fancoil is off.
The unit will restart in heating mode (anti-freeze function) if room temperature drops
below 7°C and water temperature is suitable; in this case, the red LED lamp will flash.
To restart the fancoil, rotate the knob to the operation mode required in AUTO position or
in one of the three fan speeds.
Speed selection
AUTO
The thermostat maintains the temperature of the setting by adjusting fan speed in automatic
mode, according to the room temperature and the temperature setting
The thermostat maintains the temperature of the setting by on-off cycles, using minimum,
medium and maximum fan speeds as required.
Temperature selection
Permits the required temperature to be set.
The temperature corresponding with the selector set at the central position depends on
the active functioning mode (Hot 20°C, Cold 25°C).
The differences of minimum and maximum temperature with respect to the central position are
+8°C and -8°C .
Season change
The electronic thermostat automatically sets the Cold and Hot functioning according to the temperature of the water in the system.
With special settings (that can only be programmed by qualified staff), the seasonal change is possible by adjusting the temperature
selector, the backlit displays can vary from the standard configuration.
BACKLIT DISPLAY FOR THE USER (UL PC IN THE STANDARD CONFIGURATION)
The LED indicator lamp C indicates the current operating
mode:
RED On indicates Heating operation
(heating).
Flashing indicates antifreeze mode.
RED -FUCHSIA Alternate flashing of the two colours : indica-
tes operation when hot (heating) but the water in the
system has not yet reached the temperature suitable
for enabling the ventilation.
BLUE
On indicates Cooling operation
(cooling).
BLUE -FUCHSIA Alternate flashing of the two colours : indi-
cates operation when cold (cooling) but the water in
the system has not yet reached the temperature suita-
ble for enabling the ventilation.
FUCHSIA flashing: fan coil in autotest function.
LED D: a ventilation request has been made by the electronic
thermostat:
YELLOW
On: Plasmacluster operating and ventilation
this indicates that the thermostat has
enabled,
detected a room temperature that requires the
ventilation to cut in, the PLASMACLUSTER is
activated at the same time as the ventilation
Off: ventilation not enabled, it indicates that the lou-
vre is closed and that the ventilator cannot start.
If the louvre is open, the led (D) off indicates that
selector switch A is in the OFF position or that the
room thermostat does not require start up.
Slow flashing: fan coil in standby, the ventilation is not
enabled because the water circulating in the plant
has not yet reached the right functioning tempera-
ture.
Cyclical flashing (a given no. of flashes): fan coil in
Autotest function, the number of flashes indicates the
component tested.
-
+
-
+
+
-
.
13