The dehumidifier should never be put into operation without air
filters. Dirt deposits in the drying wheel can lead to decreased
drying performance!
Air heater
The.heat.exchangers.are.maintenance-free;.however,.they.should.be.
checked.for.contamination.every.6.months.and.cleaned.if.necessary . .
In.case.of.a.defect.the.complete.heat.exchanger.unit.can.be.removed.
after.removing.the.housing.panel .
Filters
X
As necessary
Monthly
Half-yearly
Annually

09. Damaging effects on silica gel rotors

Some.of.the.substances.and.compounds.listed.below.are.typical.of.
substances.which.can.dissolve.the.honeycomb.shaped.silica.gel.rotors.
thereby.negatively.affecting.the.dehumidification.performance . .
The.sorption.rotor.should.not.be.exposed.to.air.which.is.contaminated.
with.the.following.substances.or.substances.that.are.similar.to.them . .
Even.the.smallest.of.concentrations.in.the.air.can.have.long-term.da-
maging.effects.on.the.material.of.the.rotor.and.the.sorption.capacity . .
Anorganic substances ( example )
No.
Substances
1
Lithium.chlorid
2
Sodium.hydroxide
3
Calcium.hydroxide
4
Sodium.chloride
5
Calium.chloride
6
Calcium.chloride
7
Magnesium.chloride
8
Magnesium.chloride
9
Hydroflouric.acid
10
Aluminium.chloride
11
Sea.water
12
Steam.at.high.temperature
13
Softeners
14
Strong.acids
15
Bases
15
Amines
Note:.1).Reduces.the.inner.surface.of.the.silica.gel.pores,.which.results.in.a.loss.in.performance .
B -
B -
10
9
Maintenance intervals
Rotor bearing
Motors
X
X
chem. Formula
LiCl
NaOH
KOH
NaCl
KCl
CaCl2
MgCl2
NH3
HF
AlCl3
ph.≤.2 . . .3.
ph.≥.7 . . .8.
R-NH2
Operating manual dehumidifier TTR 5000
Operating manual dehumidifier TTR 5000

Thermostats

The. electrical. switching. function. is. to. be. tested. once. per. year . . If. a.
thermostat.is.defective.it.must.be.replaced.completely .

Seals

The.circumferential.and.radial.seals.are.to.be.checked.regularly.for.
tightness.(correct.seating),.damage.and.dirt .

General

In.order.to.ensure.perfect.functioning,.the.air.dehumidification.centre.
should.be.checked.annually.for.damage,.wear.or.leakage .
Geared motor
Air heater
X
X
The.substances.in.the.list.remain.in.the.sorption.material.and.can.have.
the.following.effects:
•.Drop.in.performance.due.to.blocked.silica.gel.pores
•.Drop.in.performance.due.to.chemical.reaction.with.the.silica.gel
•.Destroys.the.mechanical.structure.of.the.rotor.through.strong.acids. .
. or.strong.bases
Effects
Reduction.in.the.effectiveness.of.the.silica.gel
Destroys.the.silica.gel.structure
Destroys.the.silica.gel.structure
Reduction.in.the.effectiveness.of.the.silica.gel
Reduction.in.the.effectiveness.of.the.silica.gel
Reduction.in.the.effectiveness.of.the.silica.gel
Reduction.in.the.effectiveness.of.the.silica.gel
Destroys.the.silica.gel.structure
Destroys.the.mechanical.strength.of.the.rotor.material
Reduction.in.the.effectiveness.of.the.silica.gel
Reduction.in.the.effectiveness.of.the.silica.gel
Destroys.the.silica.gel.structure
Blocks.the.silica.gel.pores
Destroys.the.mechanical.strength.of.the.rotor.material
Destroys.the.sorption.capacitiy..of.the.silica.gel
Reduction.in.the.effectiveness.of.the.silica.gel1)
Seals
Thermostats
X
X
1)
1)
)
1
1)
1)
1)
1)
V-belts