05. Operation with electric element heater
.
Switching on
1 . . Close.and.lock.the.control.cabinet.doors .
2 . . Turn. main. switch. and. „Schalter. Reg . . Heizung". into. position. 1 . . .
. „Störung.Phasen".lights.up . . Switch.on.„Drehfeld.Umschaltung" .
3 . . The.'Standby'.indicator.lamp.lights.up .
4 . . Press.the.'ON'.button .
5 . . The.'Standby'.indicator.lamp.goes.out.and.the.'Operation'.indicator. .
. lamp. lights. up . . If. necessary. switch. on. the. „Regelstufenabschal-.
. tung".(auxiliary.heating) .
All.drives,.including.the.heating,.are.now.switched.on.and.the.dehu-
midifier.is.operating .
ATTENTION!
THE APPLIANCE WON'T START IF THE „SCHALTER REG-HEIzUNG"
IS NOT INTO POSITION 1.
Switching off
1 . . Press.the.'OFF'.button .
2 . . The.'Operation'.indicator.lamp.goes.off.and.the.heater.and.the.pro-.
. cess.air.fan.switch.off . . The.regeneration.air.fan.runs.on.for.approx . . .
. 3-5.minutes,.in.order.to.exhaust.the.stored.heat.from.the.heater . . .
. This.running-on.is.terminated.automatically .
-..it.is.possible.to.restart.the.dryer.during.running.on .
-..the.dryer.should.only.be.switched.off.by.the.main.switch.installed.in. .
. the.mains.supply.line.in.an.emergency,.because.this.will.also.in-.
. terrupt.the.running-on.control.and.a.thermostat.error.message.can. .
. appear .
Function of the electric air heater
The.heater.consists.of.3.individual.stages . . This.results.in.an.increase.
in.the.temperature.of.the.regeneration.air.to.approx . . 120°C,.which.is.
necessary.for.the.regeneration.of.the.dryer . . Two.heating.stages.are.
always.switched.on.as.basic.load.stages .
If.the.full.regeneration.energy.is.not.required.for.the.drying.procedure,.
then.the.control.thermostat.(5B1).switches.the.control.stage.off.de-
pending.on.the.regeneration.exhaust.air.temperature . . The.regenerati-
on.temperature.is.then.reduced .
The.thermostats.are.marked.separately.and.are.accessible.by.opening.
the.service.doors .
Factory thermostat settings
Please.refer.to.the.technical.data.sheet.in.the.appendix.of.this.opera-
ting.manual .
G
06. Triggering of the safety devices and messages
Motor faults
If.the.motor.protection.breaker.for.the.regeneration.air.fan.trips.due.to.
an.overload,.then.the.dehumidifier.will.be.switched.off.automatically . . If.
the.motor.protection.breakers.for.the.process.air.fan.and.the.rotor.drive.
trip.due.to.an.overload,.then.the.dehumidifier.will.continue.in.running-on.
mode . . The.'Motor.fault'.indicator.lamp.lights.up . . Following.rectification.of.
the.fault,.the.black.reset.button.on.the.motor.protection.breaker.must.be.
pressed.again.and.the.fault.must.be.unlocked.with.the.reset.button.4S1 .
Thermostat faults
If.the.safety.or.maximum.thermostat.switches.off.due.to.over-tem-
perature,.then.the.'Thermostat.fault'.indicator.lamp.lights.up . . In.or-
der.to.restore.the.standby.condition.of.the.dehumidifier.after.cooling.
down,.proceed.as.follows:
-..Press.the.red.reset.button.on.the.maximum.temperature.limiter. .
. 4F2.and.on.the.safety.thermostat.4F1 . . Subsequently.acknowledge. .
. with.the.reset.button.4S2.on.the.control.cabinet .
Electric heater faults
The.individual.heating.stages.of.the.regeneration.air.heater.are.pro-
tected.by.over-current.trips . . In.the.event.of.a.short.circuit.or.over-
loading,.the.heating.stage.concerned.is.switched.off.and.the.'Heater.
fault'.lamp.lights.up . . After.rectifying.the.fault,.the.black.reset.button.
on.the.overcurrent.trip.must.be.pressed.again.(unlocking) .
Standby
The.electrical.power.is.connected.to.the.dehumidifier,.the.rotary.field.
of.the.mains.supply.is.correct.and.there.is.no.error . . The.dehumidifier.
can.be.switched.on.via.button.5S1 .