Transport And Installation; Transport; Installation.of.the.dehumidifier - Trotec TTR 5000 Notice D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

•..The.electrical.equipment.of.the.dehumidifier.must.be.checked.re-.
. gularly . . Repair.loose.connections.and.damaged.cables.immedia-.
. tely .
•..The. control. cabinet. must. be. kept. locked. at. all. times . . Access. is. .
. only.allowed.to.authorised.personnel.with.a.key.or.a.tool .
•..If. work. on. live. parts. is. necessary,. a. second. person. must. be. in. .
. attendance.to.turn.off.the.main.switch.in.case.of.emergency .
Service, maintenance and troubleshooting
•..The.prescribed.adjustment,.maintenance.and.inspection.work.must. .
. be.carried.out.at.the.specified.intervals .
•..Operating. personnel.must. be. informed.before.commencement.of. .
. the.maintenance.and.service.work .
•..All.plant.parts.upstream.and.downstream.of.the.dehumidfier.and. .
. operating.media.such.as.steam.must.be.secured.against.unintenti-.
. onal.switching.on .
•..Switch.off.the.dehumidifier.and.secure.it.against.being.switched.on. .
. again.for.all.service,.inspection.and.repair.work .
•..Attach.a.warning.sign.to.prevent.switching.on.again .
•..Larger.subassemblies.should.be.attached.and.carefully.secured.to. .
. lifting.devices.when.exchanging.them .
•..Check.loosened.screwed.connections.for.tightness .
•..Check.the.function.of.safety.devices.after.completion.of.the.mainte-.
. nance.work .
Structural modifications to the dehumidifier
•..The.dehumidifier.may.not.be.modified.or.converted,.nor.may.additio-.
. nal.parts.be.attached.without.the.manufacturer's.permission . . This. .
. also.applies.to.welding.on.load-bearing.parts .
•..All.conversion.work.requires.the.confirmation.of.Trotec.GmbH .
•..Machine.parts.that.are.not.in.perfect.working.order.must.be.repla-.
. ced.immediately .
•..Only.original.spare.and.wearing.parts.are.to.be.used .
•..In.the.case.of.parts.procured.from.third.parties,.it.cannot.be.gua-.
. ranteed.that.these.have.been.designed.and.manufactured.to.meet. .
. the.load.and.safety.requirements . .
Cleaning and disposal of the dehumidifier
•..Handle.and.dispose.of.used.substances.and.materials.with.care,.in. .
. particular
. -.when.working.on.lubrication.systems.and.devices
. -.when.cleaning.with.solvents .

02. Transport and installation

Transport

The.dehumidifier.may.only.be.tilted.very.slightly.during.transport . . On.
arrival.at.the.building.site,.the.appliance.must.be.checked.for.com-
pleteness.and.correlation.to.the.delivery.note.as.well.as.for.possible.
transport.damage .
B -
B -
4
3
Handling with a fork lift truck
Make.sure.that.the.forks.are.long.enough.to.take.up.the.entire.length.
of.the.appliance,.as.otherwise.the.housing.of.the.appliance.could.be.
damaged .
Handling with a crane
The.appliance.should.be.lifted.by.the.lifting.eyes . . The.tube.ends.or.the.
throttle.flaps.may.not.be.used.as.lifting.points .
Installation of the dehumidifier
The.following.points.are.to.be.considered.when.installing.the.dehu-
midifier:
•..The.appliance.must.not.be.exposed.directly.to.the.weather .
•..Ensure.that.the.lifting.device.can.take.the.weight.of.the.appliance .
•..Ensure.that.the.intended.installation.surface.is.even.and.can.take. .
. the.operating.weight.of.the.dehumidifier . . A.foundation.is.not.neces-.
. sary.for.the.dehumidifier .
•..A.space.of.at.least.800.mm.must.be.kept.free.in.front.of.the.ope-.
. rating.side.and.the.inspection.panels.of.the.dehumidifier.for.possib-.
. le. maintenance. work . . Furthermore. a. space. of. at. least. the. same. .
. width.as.the.appliance.must.be.kept.free.in.the.rotor.area.for.ex-.
. change .
•..The.dehumidifier.is.a.compact.unit . . The.customer.has.to.make.the. .
. air,.(steam).and.electrical.connections .
•..Refer.to.the.technical.data.sheet.for.the.dimensions.and.weight.of. .
. the.dehumidifier . .
•..The. connecting. cables. are. fed. through. the. cable. glands. into. the. .
. switchbox.and.connected.to.the.appropriate.terminals .
•..The.electrical.connection.must.consist.of.L1,.L2,.L3,.N.and.protecti-.
. ve.earth . . Refer.to.the.circuit.diagram.in.the.technical.appendix.of. .
. this.operating.manual.for.the.connections . . Local.regulations.must. .
. thereby.be.observed .
•..The.dehumidifier.has.been.designed.such.that.both.the.air.ducts. .
. and.the.electrical.connections.can.be.installed.simply .
•. The.following.types.of.installation.are.possible:
A . . . I n.the.room.to.be.dehumidified:.The.appliance.operates.in.air.circulati-.
. on.mode;.the.regeneration.air.outlet.is.to.be.fed.to.the.outside .
B . . . O utside.the.room.to.be.dehumidified:.The.appliance.can.be.operated. .
. in.air.circulation.or.flow-through.mode . . The.dry.air.must.in.this.case.be. .
. connected.to.the.room.to.be.dehumidified . .
In.both.cases.it.is.important.to.ensure.that.the.humid.air.outlet.is.installed.
as.far.away.from.the.process.air.inlet.as.possible .
The. piping. system. must. naturally. be. designed. to. cope. with. the.
available.static.pressure.of.the.fans . . Adjustable.throttle.flaps.at.the.
process. and. regeneration. air. outlets. allow. for. optimum. operation . .
Throttled.process.air.results.in.lower.humidity.of.the.dry.air . . Thrott-
ling.the.regeneration.air.is.useful.in.the.case.of.lower.moisture.levels .
Operating manual dehumidifier TTR 5000
Operating manual dehumidifier TTR 5000
G
G

Publicité

Table des Matières
loading

Table des Matières