Enphase Microinverter Installation
Follow the instructions in this section to install Enphase M215™ Microinverters.
WARNING: Before installing the Enphase Microinverter, read all
instructions and cautionary markings in the user manual, on the Enphase
Microinverter, and on the photovoltaic equipment.
WARNING: Perform all electrical installations in accordance with all
local electrical codes.
WARNING: Connect the Enphase Microinverter to the utility grid only
after receiving prior approval from the utility company.
WARNING: Be aware that only qualified personnel should connect the
Enphase Microinverter to the utility grid.
WARNING: Be aware that installation of this equipment includes risk of
electric shock. Normally earthed conductors may not be earthed and
may be energized when an earth fault is indicated.
Compatibility and Capacity
The Enphase M215 Microinverters are electrically compatible with most 60-cell PV
modules. For more information, see Technical Data page 24 of this manual.
Refer to the Enphase website (http://www.enphase.com/support/downloads) for
a list of electrically-compatible PV modules and approved PV racking systems.
To ensure mechanical compatibility, be sure to order the correct connector type
for both microinverter and PV module from your distributor.
Electrical Compatibility
Model Number
M215-60-230-S22
M215-60-230-S23
Capacity
Maximum number of M215s per 20 amp AC Branch Circuit
Service type
230V single phase
400V three phase
Page 8
Works with PV Module Type
60 cell
60 cell
Max M215s per AC branch circuit
Copyright Enphase Energy Inc. 2011
PV Module Connector
Type
MC-4 Type 2 Locking
Tyco Solarlock Locking
17
27
141-00017, Rev 01
e
n