BNI IOL-314-S52-P012 / BNI IOL-314-S52-P071
Network interface – Digital hub
10
Technical data (continued)
10.7
Approvals and designations
Additional information on directives, approvals and
standards can be found at www.balluff.com on
the product page.
10.7.1 CE
The CE Mark verifies that our products
meet the requirements of the current EU
Directive.
10.7.2 UL
UL requirements
File
Enclosure rating Type 1
Ambient
temperature
The power supply has to be an isolated type or SELV type.
Power Ratings
Power input, nominal
rated voltage 24 V DC
BNI IOL-...-P012
– 130 mA maximum
consumption
– 4 A including all output loads
BNI IOL-...-P071
– 130 mA maximum
consumption
– 16 A including all output loads
Power output, nominal
– max. 1,4
rated voltage 24 V DC
BNI IOL-...-P071
Digital output, nominal
– 2 A max/point (port)
rated voltage 24 V DC
– 4 A or less per unit
(BNI IOL-...-P012)
Digital output, nominal
– 4 A max/point (port)
rated voltage 24 V DC
– 16 A or less per unit
(BNI IOL-...-P071)
Cleaning
Clean the product only with dry cloth or cloth dampened
only with water!
www.balluff.com
Cord Sizes
Power In cord assembly:
Listed or R/C (CYJV2/8) cord assembly with threaded
female M12 L-coded connector rated 24 V minimum, 16 A
minimum for all models. Cord Listed S, SJ, SO, ST, SV, or
R/C (AVLV2) marked or specified in UL style page as
suitable for external interconnection rated 300 V minimum,
14 AWG minimum unless marked with maximum load
current and overcurrent protection for the cord in
accordance with table below.
Communication/Power In cord assembly:
Listed (CYJV/7) or R/C (CYJV2/8) cord assembly by Balluff
with threaded male A-coded M12 connector rated 24 V
minimum, 2 A minimum. R/C (AVLV2) marked or specified
in UL style page as suitable for external interconnection
28 AWG minimum, 300 V minimum cord. May be provided
separately as an accessory.
E319845
Communication cord assembly:
Listed (CYJV/7) or R/C (CYJV2/8) cord assembly by Balluff
with threaded female A-coded M12 connector rated 24 V
+50 °C
minimum, 2 A minimum. R/C (AVLV2) marked or specified
in UL style page as suitable for external interconnection
28 AWG minimum, 300 V minimum cord. May be provided
separately as an accessory.
In/Out cord assembly:
Listed (CYJV/7) or R/C (CYJV2/8) cord assembly by Balluff
with threaded male A-coded M12 connector rated 24 V
minimum, 2 A minimum. R/C (AVLV2) marked or specified
in UL style page as suitable for external interconnection
Cord rated 300 V minimum, 24 AWG minimum unless
marked with maximum load current and overcurrent
protection for the cord in accordance with Tab. 10-1 in
markings. May be provided separately as an accessory.
Cord
conductor
size, AWG
Overcurrent
protection
maximum
ampere rating,
Amps
Maximum
load, Amps
Tab. 10-1: Cord sizes
14 14 16 18 20 22 24 26 28 30
16 12 8 5.6 5
3
2
1 0.8 0.5
16 9
8 5.6 4 2.4 1.6 0.8 0.6 0.4
english