Installation Requirements

Installation and service of Ubbink Rolux® condensing concentric vent systems must
be performed by a qualified installer, service agency or the gas supplier.

Approvals/codes

The installation must conform with local codes or, in the absense of local codes,
the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CSA B149.1, Natural Gas
and Propane Installation Code.
The maximum vent length, as stated in the water heater installation instructions
and these instructions, should never be exceeded.

Do not use with other vent products

Ubbink Rolux® condensing vent systems must be used throughout the entire vent
system.
Do not use vent components from other vent manufacturers when using the
Ubbink Rolux® condensing vent system.
Unless approved by the appliance manufacturer, do not connect this
Ubbink concentric vent into a common vent system.

Inspection

Before installation inspect each vent component for damage and correct seal
placement. Do not attempt to fix or install any damaged vent components.

Condensate

- Slope horizontal venting 3/4 inch per foot either toward the appliance with a
condensate collector or toward the exhaust terminal (Ubbink prefers pitching the
vent 3/4 inch per foot towards the appliance with a condensate collector).
1. The vent system should be inspected annually for signs of damage or
condensate leaks. If the vent system appears damaged the appliance must be
turned off and the vent system repaired.
2. The horizontal termination may not be located above a public walkway,
driveway or area where condensate or vapor could create nuisance or hazard.
3. Ice can develop in regions of cold climate. A 3/4 inch per foot pitch to the
appliance with the use of the condensate collector is recommended (Ubbink can
not be held liable for personal injury or property damage due to ice formation).
WARNING
The Ubbink Rolux® Condensing Vent System was tested and approved
with the appliance for a maximum flue gas temperature of 230F (110°C).
Do NOT use this system on any other appliance.