Code
Reason
Text message
•
S601
Level echo in the close range not
available
Maintenance
Code
Reason
Text message
•
M500
The data could not be restored
during the reset to delivery status
Error in the deliv-
ery status
•
M501
Index markers are not continu-
ously rising, for example illogical
Error in the
value pairs
non-active line-
arisation table
•
M504
Error at a device
interface
•
M506
Error during setup
Installation/Set-
up error
•
M507
Error during setup
•
Error when carrying out a reset
Error in the in-
•
False signal suppression faulty
strument settings
Reaction when malfunc-
tion occurs
Procedure for fault recti-
The following table shows the error codes and text messages in the
status message " ut of speci cation" and provides information on
causes as well as corrective measures.
•
•
•
•
•
The following table shows the error codes and text messages in the
status message "Maintenance" and provides information on causes
as well as corrective measures.
•
•
•
•
•
•
•
•
•
10.4 Rectify faults
The operator of the system is responsible for taking suitable meas-
ures to rectify faults.
•
Evaluation of fault messages via the adjustment device
•
Checking the output signal
•
Treatment of measurement errors
Further comprehensive diagnostics options are available with a PC
with PACTware and the suitable DTM. In many cases, the reasons can
10 Diagnostics and servicing
Reduce level
Check mounting socket
Remove possible interfering
signals in the close range
Use coaxial probe
Repeat reset
into the sensor
Check linearisation table
Delete table/Create new
Exchanging the electronics
Send instrument for repair
Check and correct mounting and/
or parameter adjustment
Check probe length
Carry out reset and repeat setup
DevSpec
State in CMD 48
Bit 9 of
Byte 14 ... 24
DevSpec State
in CMD 48
Bit 0 of
Byte 14 ... 24
Bit 1 of
Byte 14 ... 24
Bit 4 of
Byte 14 ... 24
Bit 6 of
Byte 14 ... 24
Bit 7 of
Byte 14 ... 24
63