Balluff BMD 1L K Série Notice D'utilisation page 151

Sonde de mesure tige et câble avec qualification sil
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Setup - Application - Di-
electric constant
Setup - Max. adjustment
Level
Setup - Min. adjustment
Level
This menu item is only available if you have selected interface meas-
urement under the menu item "Application". In this menu item you can
enter the dielectric constant of the upper medium.
You can directly enter the dielectric constant of the upper medium or
have the value determined by the instrument.
If you want the dielectric constant to be determined by the instrument,
you have to enter the measured or known distance to the interface.
In this menu item you can enter the max. adjustment for the level. With
interface measurement this is the maximum total level.
Adjust the requested percentage value with [+] and store with [OK].
Enter the appropriate distance value in m (corresponding to the
percentage value) for the full vessel. The distance refers to the sensor
the max. level must lie below the dead band.
In this menu item you can enter the min. adjustment for the level. With
interface measurement this is the minimum total level.
Adjust the requested percentage value with [+] and store with [OK].
7 Set up with the display and adjustment module
37