2 - INSTALLATION

2.1 - INSTRUCTIONS FOR INSTALLATION

To obtain the best results and optimum performance, follow the instructions for correct installation provided
in this manual.
A failure to implement the indicated standards, which may cause a malfunction
of the appliances, relieves OLIMPIA SPLENDID from any form of warranty and
from any liability for possible damages caused to people, animals or things.
The electrical system must be compliant with legal standards, must respect
the data in the technical data sheet and be must be equipped with an efficient
ground system.
The appliance shall be installed in such a position that maintenance can be
carried out easily.

2.2 - INSTALLATION OF THE INTERNAL UNIT

Prepare:
A free space, sufficient to allow the removal of the guards, the connection of the water and refrigerant
pipes and ordinary or extraordinary maintenance.
A water drain nearby
A compliant electrical power supply, near the internal unit
Water feeding for filling of the hydraulic circuit
Communication cable between internal and external unit (see par. 3.4.2)
The internal unit must be installed supported by the floor in an indoor environment and levelled using
the adjustable feet (pos. A - Fig.4).
For the installation spaces and the position of the pipes, please refer to paragraph "Hydraulic connec-
tions" and to "Fig.5".
Connect the wire way (X) for condensation drain to the hole positioned in
the rear part of the tray and make it come out from one of the two holes
located in the lower part of the back of the unit.
Opportunely close the unused hole
2.2.1 - Removal of the front panel (Fig.3)
Open the upper door (S) rotating it upwards.
Undo the fixing screw (X) of the front panel (P).
Tilt the top part of the front panel (P) towards yourself and raise it upwards to release it from the pins on
the unit base.

2.2.2 - Access to internal components

After removing the front panel, remove the two screws (V) which fix the cover of the electric panel (Q).
(Fig.6).
Remove the four screws (V1) and rotate the panel rightwards to have access to the components behind
the electric panel (Q). (Fig.6a).