2.4 - OPERATIONAL LIMITS
The charts define water temperature (LWT) and external air (ODT) limits within which the heat pump can
work in the two cooling modes, heating and domestic water production (DHW).
HEATING
ODT
35
30
-9
-20
5 12
35
The parts highlighted in grey show the moment in which the electric heaters intervene in addition to the
main circuit.
3 - CONNECTIONS
3.1 - REFRIGERANT CONNECTIONS
To define the refrigerant connection lines between the internal and external units, refer to the table below.
Maximum length of the connection pipes (m)
Elevation difference limit between the two units if the external
unit is positioned higher (m)
Elevation difference limit between the two units if the external
unit is positioned lower (m)
Additional load of refrigerant per metre beyond 10 metres of
pipes (g/m)
Exclusively use pipes with diameters which respect the required dimensions.
The maximum length of the connection lines to the internal unit MUST be in compliance with the table
in paragraph "3.1", topping up the load of R410A as intended (see par.3.1.2). Do not install the units
beyond the maximum permitted difference in level between internal unit and external unit.
COOLING
ODT
46
20
10
-5
LWT
55
60
5
12
DOMESTIC WATER
ODT
43
30
-2
-20
LWT
25
5 12
SHERPA TOWER S2 BIG
ACS
LWT
42 50
60
50
30
25
54
EN - 11
TOWER BIG