Failure to have filter fitted during operation will
cause serious damage.
The refrigeration circuit inside the room unit is
fitted with a HIGH and a LOW pressure sensing
switch. They are both manually resettable. A pen-
cil or screwdriver with gentle pressure on the knob
behind is all that is required to reset. Necessary
access is provided either via the lower front panel
on PAC4500AX/ET4500AX and through the control
console of the PAC6500AX.
Problem: No Cooling.
Diagnosis: Amber „ATTENTION" light illuminated.
Low pressure trip.
Cure:
Press, „-" button to reset and check for
No air flow, blocked filter? Evaporator
blocked with ice. Very low air tempera-
ture?
Problem: No cooling (PAC6500AX).
Diagnosis: Amber „ATTENTION" light illuminated.
High level condensate trip.
Cure:
Condensate pump not reducing water
level. Kink in condensate tube between
room unit and external heat exchanger?
Leak inside room unit. Sump filter inside
room unit blocked. Condensate tube
frozen.
Problem: No cooling (ET4500AX).
Diagnosis: A mber „ATTENTION" light illuminated.
Bottle fitted switch trip.
Cure:
ET4500AX with pump kit. Ensure link
fitted to terminal block.
ET4500AX with bottle. Ensure bottle
fitted / fitted correctly.
Problem: No cooling (PAC4500AX/ET4500AX).
Diagnosis: Amber „CONTAINER FULL" light illumi-
nated. High level condensate trip.
EN
Cure:
fessionally in accordance with Directive 2002/96EU of
the European Parliament and Council of 27th January
2003 concerning old electrical and electronic equip-
ment. At the end of its life please dispose of this ins-
trument in a manner appropriate to the relevant legal
requirements.
Bedienungsanleitung – Klimagerät PortaTemp 4500 / 6500 AX
PAC4500AX As PAC6500AX.
ET4500AX With condensate kit - As
PAC6500AX.
ET4500AX With bottle.
Remove and empty container, then replace
in machine. In the European Union electro-
nic equipment must not be treated as do-
mestic waste, but must be disposed of pro-
B - 6