05. care & MaIntenance
The air filter must be kept clean, never allow to be-
come choked with dust or dirt. If allowed to do so, the
performance of the unit will become impaired, resul-
ting in loss of air flow, freezing up of the evaporator
coil and possible component damage.
ACCESSING THE FILTER PAC4500AX/ET4500AX
Open the lower front panel, filter is located in front
of the evaporator. A second filter is fitted to the rear
panel on of an ET4500AX.
PAC5600AX Lift out the return air grille on the front
face of the unit, Fig 4. On refitting the filter ensure
that it is correctly positioned covering the whole
rear face of the grille. The filter (see Fig. 4) can be
washed in warm, soapy water, rinsed and shaken dry
before replacement. Frequency of cleaning depends
upon application and can only be determined by the
user. However, you should never allow more than two
months to elapse between cleaning. The probable
life of the filter will be about one year and spares are
available from the supplier of the unit itself.
B - 5
LIFT AND
REMOVE
AIR FILTER
(PT 6500 AX)
UNSCREW RETAINERS AND
OPEN PANEL, REMOVE FILTER
PAC4500AX/ET4500AX
Bedienungsanleitung – Klimagerät PortaTemp 4500 / 6500 AX

06. trOUBleshOOtInG

Only a competent electrician should attempt to
rectify electrical supply problems. Do not remo-
ve any panels from the machine.
Problem: No air flow from room unit.
Diagnosis: R ed „MAINS" light off.
Cure:
Turn on electricity and/or check mains
supply fuse.
Problem: No air flow from room unit.
Diagnosis: R ed „MAINS" light on, White „DEFROST"
light on.
Cure:
Machine in defrost mode, do not adjust
anything, machine will revert to normal
run after 10 mins.
Problem: Insufficient air flow from room unit.
Diagnosis: B locked air filter.
Cure:
Clean filter.
Problem: No cooling.
Diagnosis: Green „COOLING" light off.
Cure:
Revolve thermostat knob fully anticlock-
wise to „1". Wait 10 minutes for time delay
on start-up.
Problem: No cooling.
Diagnosis: A mber „ATTENTION" light illuminated.
High pressure trip.
Cure:
Press „+" button to re-set and check for :
- Lack of water flow: kinked hoses? Shortage of water:
top up.
- External heat exchanger unit mounted in very high
temperature? Water frozen? Add glycol (33%).
- External heat exchanger coil blocked with dirt: clean.
- A ir cooled units: lack of air flow from exhaust: kinked
or blocked duct, duct too long.