MCS5, MCS15
8.6
Restore Memorized Default Settings
The memorized default settings can be restored as follows.
Enter the Program Mode.
Set P-17 to "rSt".
Exit the Program Mode.
The software version number (e.g. "A12") appears in the display.
The memorized default settings are restored and the Marine Climate Sys-
tem returns to the Off Mode.
8.7
Programmable Parameters
Programmable Parameters Table
Program
Description
number
P-1
Operating Mode
P-2
High Fan Speed Limit
(arbitrary units)
P-3
Low Fan Speed Limit
(arbitrary units)
P-4
Compressor Staging
Time Delay
P-5
Temperature Sensor
Calibration
P-6
Failsafe
P-7
Low AC Voltage Shut-
down (Volts)
P-8
De-Icing Cycle
P-9
High Water Tempera-
ture Limit (°F)
Default
Range
0
0 = Automatic mode
1 = Cool only mode
2 = Heat only mode
95
65 – 95
55
30 – 64
15
5 – 135 s
Ambient
Ambient 10 °F
Temperature
3
0 = Minimum protection
1 = Continuous, no display
2 = Continuous, with display
3 = Four failures, reset required
115 V – OFF
75 – 105
220/230 V – OFF
175 – 205
1
OFF
1 = On with 5 °F faceplate sensor
differential
2 = On with 7 °F faceplate sensor
differential
OFF
100 – 150
Programming