Mechanical Coding Of The Plug-In Module; Electrical Connections - Camille Bauer SIRAX SV 824 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Effectiveness of
input monitoring:
Enbalbed or disabled by switch
"
If the amplifier is a contact instead
of an active sensor and the input
circuit has to be monitored, two
resistors must be fitted close to the
contact as shown in Fig. 3.
Fig. 3. Input contact circuit.
Power supply H
AC/DC module (DC and 45...400 Hz)
Table 2: Nominal voltages and tolerances
Nominal voltage U
N
24... 60 V
DC / AC
85...230 V
AC
85...110 V
DC
Power input:
≤ 1.4 W resp. ≤ 2.7 VA
Electrical
isolation:
Signal inputs to output contacts
and power supply
Regulations
Electromagnetic
compatibility:
The standards DIN EN 50 081-2
and DIN EN 50 082-2 are observed
Intrinsically safe:
Acc. to DIN EN 50 020: 1994
Electrical standards:
Acc. to IEC 1010 resp. EN 61 010
Protection:
(acc. to IEC 529
resp. EN 60 529):
Housing IP 40
Terminals IP 00
Ambient conditions
Commissioning
temperature:
–10 to + 55 °C
Operating temperature: –20 to + 55 °C *
Storage temperature:
– 40 to + 70 °C
Relative humidity
of annual mean:
≤ 75%
* The data of the EC-type-examination Certificate for backplane
SIRAX BP 902 with admission PTB 97 ATEX 2113 should be noted.
".
1 to 2 kΩ
R
≤ 200 Ω
Ltg
Mecha-
10 to
nical
SIRAX SV 824
15 kΩ
contact
Control circuit
Tolerance
DC – 15...+ 33%
AC ± 15%
± 10%
– 15...+ 10%

6. Mechanical coding of the plug-in module

Where there is a danger of inserting a module in
the wrong slot, the possibility has to be excluded
as prescribed in EN 50 020, Section 6.3.2. To this
end, the units must be supplied already equip-
ped with coding inserts as shown in Figure 4.
Order Type
130 162
Back
A
B
C
D
E
F
G
H
I
K
L
M
Power supply
24...60 V DC/AC
Fig. 4. Coding of the plug-in module SIRAX SV 824.
= With set of code,

7. Electrical connections

The isolating switch amplifier SIRAX SV 824 is plugged
onto a backplane BP 902. A 96 pin connector (model C,
DIN 41 612) establishes the electrical connections between
the isolating switch amplifier and the backplane. The pin
connections can be seen from Fig. 5.
Please refer to our backplane instructions for the back-
plane wiring.
Make sure that the cables are not live when
making the connections!
The 230 V power supply and 250 V contact
output is potentially dangerous!
The supplementary information given on the
EC-type-examination Certificate and also
local regulations applicable to electrical
installations in explosion hazard areas must
be taken into account!
130 170
Back
A
B
C
D
E
F
G
H
I
K
L
M
Power supply
85...110 V DC /
85...230 V AC
= Without set of code