aldes EasyVEC C4 Notice D'installation page 29

Masquer les pouces Voir aussi pour EasyVEC C4:
Table des Matières

Publicité

EN
Adress
Category
(Decimal)
1
3
12
Identifi cation
20
21
34
BMS Ventilation
Operating mode
256
272
274
276
284
285
Operating
286
setting
287
288
289
291
292
Main entries
Supply
337
0-10V entry
338
C4 Mode
366
384
386
388
390
Errors
392
394
396
398
400
Machine reboot
65534
Adress
Data
(Hexa)
$1
Machine ID code
$3
Aldes serial number
$C
Software version
Back-up order
$14
Parameters
$15
Box fan number
$22
Product ID
$100
Control mode
$110
Exhaust Flow setpoint
Extract Pressure
$112
setpoint
$114
speed setpoint
$11C
Parameter 0-10V U1
$11D
Parameter 0-10V U2
$11E
Parameter 0-10V V1
$11F
Parameter 0-10V V2
$120
Parameter P1
$121
Parameter P2
$123
Nbr. Eyes
$124
gas option
$151
Power supply voltage
$152
0-10V input
$16E
Mode C4 state
$180
Current error code
$182
Previous error code
$184
N-2 error code
$186
N-3 error code
$188
N-4 error code
$18A
N-5 error code
$18C
N-6 error code
$18E
N-7 error code
$190
N-8 error code
$FFFE
Card restart
Read
Write
Size
(Words)
(0x03)
(0x10)
2
x
4
x
1
x
1
x
x
1
x
1
x
x
1
x
x
1
x
x
1
x
x
1
x
x
1
x
x
1
x
x
1
x
x
1
x
x
1
x
x
1
x
x
1
x
x
1
x
x
1
x
1
x
1
x
1
x
1
x
1
x
1
x
1
x
1
x
1
x
1
x
1
x
1
x
29
Comments
SAP code
EasyVEC®: Storing $1213, Reset C4: $5452
Constant pressure self-balancing = 12
Constant pressure self-balancing = 12
Constant pressure humidity-controlled = 13
Constant pressure TFlow = 14
Constant airfl ow = 1001
Constant speed = 2
Rising curve auto = 1002
Rising curve hygro = 1003
Rising curve TFlow = 1004
Rising curve Expert = 1005
0-10 V = 1006
0 = shutdown, 2512 = active
If 0xFFFE sent, the card then is reset and the
commissioning will be eliminated