B.3. Mode Expert • Expert Mode - aldes EasyVEC C4 Notice D'installation

Masquer les pouces Voir aussi pour EasyVEC C4:
Table des Matières

Publicité

CONTROLS
Controlled P.
In the event of a controlled pressure operating mode, two pressure values are required by the box fan to operate:
- Minimum pressure (Pmin): it is defined automatically according to the type of ductwork: Hygro, T.Flow or Auto. Select the type of
corresponding ductwork and confirm.
- 95 Pa for the humidity-controlled mode (Hygro) when EasyVEC C4 ULTRA or ULTIMATE is combined with a standard system on humidity-
controlled terminals (without thermodynamic water heater connected to the exhaust air),
- 135 Pa for the humidity-controlled mode + T.Flow (T. Flow) when EasyVEC C4 ULTRA or ULTIMATE is combined with a T.Flow Hygro+ and
T.Flow Nano on humidity-controlled terminals,
- 75 Pa for the self-balancing mode (Auto) when EasyVEC C4 ULTRA or ULTIMATE is combined with a standard system on self-balancing
terminals
CONSIGNE
P = 120 Pa
- La pression maximale (Pmax) : elle doit être saisie manuellement. Il est fortement recommandé de renseigner la valeur indiquée dans le
rapport d'étude Conceptor Ventilation. Diminuer ou augmenter la consigne avec
SETPOINT
P = 120 Pa
- Maximum pressure (Pmax): it has to be entered manually. It is highly recommended to insert the value indicated in the Ventilation Conceptor
study report. Reduce or increase the setpoint with
b.3. Mode Expert • Expert Mode
Sélection chiffre en clignotement et non souligné • Selection figure blinking and not underlined
Pour accéder au menu Expert il est nécessaire de renseigner le code PIN : 4144 • To access the Expert menu, the following PIN code has
to be entered: 4144
RÉGULATION
Expert
Sur les modèles ULTRA et ULTIMATE, le mode expert permet : • On the ULTRA and ULTIMATE models, the expert mode allows:
• De renseigner dans le mode Pression régulée les pressions Min et Max manuellement pour ajuster le fonctionnement du caisson à
l'installation : • The Min. and Max. pressures to be entered in the controlled pressure mode to adjust the operation of the box fan at
installation:
EXPERT
Press. Régulée
... Vitesse Constante
• Un pilotage par vitesse constante : • Control by constant speed:
EXPERT
Vitesse Constante
... Q Constant
CONTROLLED P
Humidity-based
®
... T.Flow
CONSIGNE
P = 130 Pa
SETPOINT
P = 130 Pa
or
and press
CODE PIN
4 1 4 4
P. RÉGULÉE
Press. min.
... Press. max.
EXPERT MODE
Constant speed
... Constant airflow
18
CONSTANT P
Humidity-based
... T.Flow
®
CONSIGNE
P = 130 Pa
ou
et appuyer sur
SETPOINT
P = 130 Pa
to confirm.
CONTROLS
Expert mode
EXPERT MODE
Constant press
... Constant airflow
pour valider.
PIN CODE
4 1 4 4
CONTROLLED P
Minimum press.
... Maximum press.