maximum 0.3 MPa/3 bar/43.5 psi, the same as for load and leak tests for gas
pipes, in agreement with the responsible industrial liability insurance associa-
tion and based on these rules. The national regulations are thereby fulfilled."
The respective national safety provisions, rules and regulations valid for
the application site must be considered and observed.
Before conducting a test with compressed air, it must be assessed whether the
installation to be tested will withstand the preset / selected test pressure "p
refer".
Connect the compressed air hose (Fig. 4 (23)) to the output Pressure test with
compressed air, Disinfection, Cleaning, Preservation, Compressed air pump
(22) and connect the compressed air hose (23) to the installation to be tested.
2.6.2. Pressure and leak test with water in accordance with EN 806-4:2010
(only ROLLER'S Multi-Control SLW)
WARNING
The hydro-pneumatic water pump installed additionally in the ROLLER'S
Multi-Control SLW for this test is fed by the built-in compressor of the ROLLER'S
Multi-Control. The hydro-pneumatic water pump generates a water pressure
of max. 1.8 MPa/18 bar/261 psi. Before conducting one of the tests with water
according to method A, B, C, it must be assessed whether the installation to
be tested will withstand the preset/selected test pressure "p refer".
Fit the ROLLER fine filter (12) (Art. No. 115323) with filter cartridge 50 µm after 
the house connection (water meter). Connect the suction/pressure hose (13)
to the pressure test with water supply (Fig. 1 (24)) after the fine filter. Connect 
the high-pressure hose (26) to the pressure test with water drain (Fig. 4 (25))
and connect to the installation to be tested. Feed the pressure relief water drain
(27) into a vessel (bucket).
2.7. Compressed air pump program
Vessels of all types can be pumped up with this program. Connect the compressed
air hose (23) to the output Pressure test with compressed air, Disinfection,
Cleaning, Preservation, Compressed air pump (Fig. 4 (22)) and connect it to
the vessel to be pumped up, e.g. expansion vessel, tyre. The default is displayed
as 0.02 MPa/0, 2 bar/3 psi.
2.8. Memory Manager program (data transfer)
The results of the flushing and test programs are saved with date, time and log 
number in the selected language and can be transferred to a USB stick or
printer (neither of which is included in the scope of supply) for documentation.
2.9. Compressed air tools connection
Unlike the described "Compressed Air Pump" program in which the values are
controlled by the electronic control, compressed air tools up to a max. air
requirement of 230 Nl/min can be operated directly from the compressed air
vessel at the compressed air tools connection (Fig. 4 (28)). A compressed air
hose with quick couplings NW 7.2 must be used (available as an accessory).
3. Operation
Before using the ROLLER'S Multi-Control, check whether the respective latest
version software is installed on the input and control unit. Select the Settings
menu and then Device data to display the version software. The latest version
software (Ver. Software) for the input and control unit is available by USB stick
as a download under www.albert-roller.de → Downloads → Software. Compare 
the number of the version software with the latest version software number and
install the latest version software on the input and control unit by means of a
USB stick if necessary. See 2.3 for the further procedure.
NOTICE
The defaults for the different test criteria (test sequences, pressures and times)
in the settings menu of the ROLLER'S Multi-Control are taken from EN 806-4:2010
or the information leaflet T 82-2011 of the German Central Association for 
Sanitary, Heating and Air Conditioning. All defaults for the test programs can
be edited by the user in the Settings menu and in the Flushing, Test with
compressed air, Test with water and Compressed Air Pump programs. Changes
in the Settings menu are saved, i.e. they reappear the next time the ROLLER'S
Multi-Control is switched on. If the defaults are only changed in one of the
programs, the original defaults appear again the next time the ROLLER'S
Multi-Control is switched on. Reset resets all defaults to factory settings and
the language to German (deu) and the date, time, units formats to DD.MM.
YYYY, 24 h, m / bar.
Attention: The user is solely responsible for transferred or newly entered
test criteria (test sequences, pressures and times) or defaults in the
individual programs and the conclusions from the tests. Especially, the
user must decide whether a prescribed stabilisation/wit time is ended
and must confirm this by \Enter.
The respective national safety provisions, rules and regulations valid for
the application site must be considered and observed.
The electronic memory of ROLLER'S Multi-Control holds 40 files (logs). A soon 
as a program has been selected from the Start menu and the selected data
have been confirmed with Enter, a new file no. is created automatically even if 
the program is then abortede.g. with Esc. If the 40th memory location is occu-
pied, the message "Last file no. available". After completing this process, all
files should be copied to a USB stick via the USB port (Fig. 2 (33)). The oldest 
file no. in the memory is then overwritten when further files are saved. 
Screen display (must be released by Enter):
000425
Consecutive file no. 000425
19.08.2013 10:13
Date 19.08.2013    Time 10:13 (creation of a new file no.)
Files 40/40
Files 40/40 (a max. of 40 files are saved)
Last file no.
Last file no.
available
available
3.1. Flushing of drinking water installations programs
The flushing methods "flushing with water" and "flushing with water/air mixture 
with pressure pulses" are described in EN 806-4:2010 and for Germany addi-
tionally in information leaflet T 84-2004 "Flushing, Disinfection and Commissioning 
of Drinking Water Installations" of the German Central Association for Sanitary,
Heating and Air Conditioning. ROLLER'S Multi-Control additionally offers the
flushing program "flushing with water/air mixture with constant compressed 
air".
Excerpt from EN 806-4:2010, 6.2.1. "The drinking water installation must be
flushed with drinking water after installation and pressure testing as well as 
immediately before commissioning." "If a system is not put into operation
immediately after commissioning, it must be flushed at regular intervals (up to 
7 days)."
3.1.1. Flushing with water program (without air supply)
In accordance with EN 806-4:2010 and information leaflet T 84-2004 of the 
German Central Association for Sanitary, Heating and Air Conditioning, the
drinking water used for flushing must be filtrated whereby particles ≥ 150 µm 
must be held back and the water must be perfectly fit for drinking (ROLLER 
fine filter with filter cartridge 50 µm, Art. No. 115323). The system must be 
flushed section for section depending on the size of the installation and the 
arrangement and lay of the pipes. The minimum flow velocity when flushing 
the installation must be 2 m/s and the water in the system must be replaced at
least 20 times during flushing.
For Germany the following is prescribed additionally among other things in the
information leaflet T 84-2004 of the German Central Association for Sanitary, 
Heating and Air Conditioning: "Flushing will take place floor by floor from the 
end of the rise pipe. Within the floor and single lines, at least as many tapping 
points as listed in Table 1 as a recommended value for a flushing section will 
be fully opened for at least 5 minutes floor by floor. 
Greatest rated width of the pipe in the
flushed section, DN
Greatest rated width of the pipe in the flushed 
section, in inches
Minimum number of tapping points to be
opened DN 15 (½")
Table 1: Recommended value for the minimum number of tapping points to be
opened related to the greatest rated width of the distribution line" (Information
leaflet T 84-2004 of the German Central Association for Sanitary, Heating and 
Air Conditioning, lines in italics added, limiting to DN 50)
ROLLER'S Multi-Control displays the achieved flow velocity and the achieved 
water change on the screen among other things.
Program sequence ↑ ↓ (8):
1. Flush \ Enter
2. without compressed air \ Enter
3. Check default max. DN according to table 1 and change if necessary
(11) \ ↓
4.  Enter water volume of the flushing section VA H
5.  Open the water supply. The values flash as long as the minimum flow 
velocity v H
O = 2 m/s and the water change n H
2
reached. On reaching the values \ Enter
(If the defaults v H
O and n H
2
cause, repeat the process)
6. Display screen: Water pressure (p H
flushing time (t H
O), water change (n H
2
\ Enter
7. Esc >> Start menu \ Memory Manager, data transfer >> 3.6
3.1.2. Flush with water/air mixture with intermittent compressed air program
The cleaning effect by flushing can be reinforced by adding compressed air. 
In accordance with EN 806-4:2010 and information leaflet T 84-2004 of the 
German Central Association for Sanitary, Heating and Air Conditioning, the
drinking water used for flushing must be filtrated whereby particles ≥ 150 µm 
must be held back and the water must be perfectly fit for drinking (ROLLER 
fine filter with filter cartridge 50 µm, Art. No. 115323). "The pipe system can be 
flushed under pressure with a drinking water/air mixture intermittently with a 
minimum flow velocity in every pipe section of 0.5 m/s. A certain minimum 
number of tap fittings must be opened for this. If the minimum volume flow is 
not reached with full filling of the distribution pipe in a section of the pipe system 
to be flushed, a storage tank and a pump must be used for flushing." "The 
system must be flushed section by section depending on the size of the instal-
lation and the lay of the pipes. No flushing section may exceed a pipe section 
length of 100 m."
25
32
40
1"
1¼"
1½"
2
4
6
O (0-999 l) \ Enter
2
O = 20 have not been
2
O are not reached: \ Esc = cancel, clarify the
2
O), minimum flow velocity (v H
2
O), volume of used water (V H
2
eng
50
2"
8
O),
2
O)
2