Operating in MODE 2 and external set value control.
The set value is controlled by the input signal 0-10V or 4-20mA.
For the starting up, we recommend to set the motor speed at 60% of
its maximum pressure.
With a short impulse on the touch pad the actual pressure can be
displayed; the requirement pressure reappears after 30 seconds or
after on other impulse.
An impulse ~1s allows the ON/OFF function.
- Select OFF.
- Validate.
Note : the remote control (ex : switch) allows a stop of the pump
(variator ON).
When stopping the pump, the sign "OFF" appears.
MODE 2 : Other regulation
Parameters input in MODE 2
- Set the switch (fig. 4 - item S) on position SERVICE.
- Select "M2".
- Validate.
- Select the source of set value Internal/External,
Default "I"
(set value adjustment by touch pad)
- Validate.
- If the external set value "E" is validated,
(set value adjustment by external signal)
Select the signal type (0-10V) or (4-20mA).
- Validate.
- Select the regulation type "O" for other regulation.
- Validate.
- Select the type of sensor (0-10V) or (4-20mA).
(the information which is blinking is the one validated).
- Validate.
- Display "P" parameter of PID.
- Validate.
- Select "P" value.
(Default P=1).
- Validate.
- Display "I" parameter of PID.
- Validate.
- Select "I" value.
(Default I=1s).
- Validate.
- Display "D" parameter of PID.
- Validate.
- Select "D" value.
(Defaut D=0ms)
- Validate.
- Visualisation of the Operating time meter.
(number of pump operating hours).
- Validate.
- Set the switch back on position "OPERATION".
0,1s
0,1s
MODE 2 - Other regulation
ON
ON
25
1s
0,1s
SERVICE
1
2
0,1s
0,1s
0,1s
0,1s
0,1s
0,1s
0,1s
0,1s
0,1s
0,1s
0,1s
0,1s
OPERATION
1
2