MEDC PBE Manuel Technique page 37

Declencheur à bouton poussoir
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

BGI/BGW:
The unit is operated by the breaking of the glass. Due to the design of the unit, there is no need to use a hammer
and the operator is protected from the broken glass by the vinyl glass label.
D
NOT
Replacement of the glass:
To replace the glass after operation of the unit, remove the small cover held in place by the 2 slotted screws. Take
out the glass and remove any broken fragments from the unit. Place the new glass into the unit and replace the
e
cover, then test the unit as described below.
Testing the unit:
Using the test key provided, insert the key into the test hole (situated on bottom right hand side of the glass
cover) and engage into test cam. Turn the key in a clockwise direction (approx. 60°). This will simulate the
breaking of the glass. Release the key to reset the callpoint.
NOTE: MEDC DO NOT recommend forcing the test key further than 80° clockwise or 0° anti-clockwise as
this may lead to premature failure of the test cam.
P
PBI/PBW:
D
NOT
The unit is operated by lifting the flap and pressing the plunger. This will either:
1.
R
emain in its
actuat
2.
Return to its original position on release - spring return
ote: On the turn and push units,
to actuation.
Testing the unit:
To test the unit, press the plunger as explained above.
4. MAINTENANCE
During the working life of the unit, it should require little or no maintenance. However, if abnormal or
unusual environmental conditions occur due to plant damage or accident etc., then visual inspection is
recommended.
If a unit fault should occur, then the unit can be repaired by MEDC. All parts of the unit are replaceable.
If you acquired a significant quantity of units, then it is recommended that spares are also made available. Please
discuss your requirements with the Technical Sales Engineers at MEDC.
07/15
ed
position (the plunger can be reset by using the key supplied) – latching type.
there is no lift flap fitted and
the plunger must be rotated through 90° prior
© MEDC 2015