tau K995MA-S Notice D'installation page 16

Masquer les pouces Voir aussi pour K995MA-S:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

DIP-SWITCH
AUTOMATIC
1
CLOSING
2
2 / 4 STROKE
NO
3
REVERSE
4
PHOTOTEST
PRE-
5
FLASHING
FORCE IN STORAGE
6
PHASE
7
BACKJUMP
GARAGE DOOR
8
SELECTION
9
DECELERATION
IMPORTANT: the position of the sectional opening limit switch is uploaded during se-
tup ONLY the first time the procedure is carried out (LEDs DL1 and DL2 alternating red
/ green light). To change the position it is necessary to carry out, before a new setup
procedure, a "FACTORY RESET" (see page 9).
SENSITIVE
10
EDGE
IMPORTANT:
Each pair of terminals attached to an NC contact that is not in use must be short-circuited in
order to ensure the proper operation of the board.
5. PROCEDURE FOR STORING ANY BUS ACCESSORIES
ATTENTION: After powering the control panel, wait for 2 seconds before starting to carry out
the adjustment maneuvers.
If there is a need to equip the automation with any accessories such as photocells, flashing light, key
when opening is complete, the closing of the sectional door is automatic
after 60 sec.
On
NOTE: the adjustment of the automatic closing time can be carried
out ONLY via TAU APP (with T-WIFI device)
Off
automatic closing disabled.
with automatic closing enabled, a sequence of open/close commands
On
causes the sectional door to OPENCLOSE-OPEN-CLOSE etc.
in the same conditions, the same command sequence causes the sec-
Off
tional door to OPEN-STOP-CLOSESTOP-OPEN-STOP (step-by-step).
On
during opening the sectional door ignores any closing commands.
the sectional door's behavior depends on the position of dip switch No.2.
Off
The direction can be reversed also during the opening manoeuvre.
On
the "BUS photocells check" function is enabled.
the "BUS photocells check" function is disabled.
Off
Note: leave in OFF position when photocells are not used.
preflashing enabled, each time the gate is operated the light starts flash-
On
ing 3 seconds before the gate begins to move.
Off
when the gate is started, it will move immediately.
Force value increased during the storage phase for sectional doors with
On
sliding problems during opening / closing
Normal force value during the storage phase for sectional doors wi-
Off
thout sliding problems during opening / closing
On
parameter increased for the realignment of the belt / chain after closing.
Off
standard parameter for the realignment of the belt / chain after closing.
On
use for overhead door with 100BANT accessory
Off
use for sectional door
parameter increased for the deceleration point of the sectional door in
On
the opening / closing phase.
standard parameter for the deceleration point of the sectional door in
Off
the opening / closing phase.
resistive sensitive edge connected. Connect the resistive sensitive edge,
On
with the related 8,2 KΩ resistance, to terminals 1-3.
SENSITIVE EDGE WITH NORMALLY CLOSED CONTACT (N.C.) Connect the
Off
sensitive edge to terminals 1-3.
Note: If no sensitive edge is used, set the DIP SWITCH 10 to OFF and
short-circuit the terminals 1-3.
16

Publicité

Table des Matières
loading

Table des Matières